What a Standpipe System Does
A standpipe is a system of vertical and horizontal piping with hose connections that delivers water to where firefighters need it inside a building. Rather than dragging hose up many flights of stairs from the street, firefighters connect their hose to a valve on the fire floor that is already supplied with water. NFPA 14, the Standard for the Installation of Standpipe and Hose Systems, governs the design. Standpipes are essential in high-rise buildings, large-area structures, and buildings where travel distance to the fire would otherwise be excessive.
The Three Classes of Standpipe
NFPA 14 classifies standpipe systems by who is expected to use them and what hose connection they provide.
- Class I systems provide 2.5-inch hose connections intended for use by the fire department and trained personnel. They are sized for the high flows of professional firefighting and are the most common type in high-rise buildings. No hose is stored; firefighters bring their own.
- Class II systems provide 1.5-inch hose connections with hose intended for use by building occupants or a fire brigade during the early stages of a fire. Modern codes have largely de-emphasized Class II because untrained occupants are now generally directed to evacuate rather than fight fires.
- Class III systems combine both: they provide 2.5-inch connections for the fire department and 1.5-inch connections for occupant or first-aid use, serving the purposes of both Class I and Class II.
Hose Connection Placement
Hose connections must be located so that all portions of each floor are within reach of a hose stream. For Class I systems, connections are generally required in every exit stairway at each floor level and at additional locations as needed to cover the floor area, so that no point on the floor is beyond the design hose lay plus a nozzle reach. The standpipe in the stairway keeps the firefighters in a protected location while they connect and advance their line. Roof connections and connections at intermediate landings may also be required depending on the building configuration.
Minimum Pressures and Flows
The defining hydraulic requirement of a Class I or III standpipe is the pressure available at the hose connection. NFPA 14 requires a minimum residual pressure of 100 pounds per square inch at the hydraulically most remote 2.5-inch hose connection while flowing the design demand. (Earlier editions used 65 psi; the higher value reflects the needs of modern fog nozzles and longer hose lays.) For 1.5-inch connections serving occupant use, the minimum residual pressure is 65 psi.
Flow is built up from the standpipes. The most remote standpipe must supply 500 gallons per minute, and each additional standpipe adds 250 gallons per minute, up to a maximum total system demand that NFPA 14 caps (commonly 1,000 gallons per minute for fully sprinklered light- and ordinary-hazard buildings, and higher where sprinklers are absent). The water supply, often a fire pump, must deliver this combined flow at the required residual pressure simultaneously.
Zoning Tall Buildings
In a tall building, elevation alone creates enormous pressure differences. Roughly 0.433 psi of static pressure is gained for every foot of height, so a column of water 230 feet tall imposes about 100 psi of static head. If a single pump pressurized the entire height, the lowest floors would see dangerously high pressure while the top floors barely met the minimum. NFPA 14 therefore limits the maximum static pressure (commonly to about 350 psi at any point with standard components) and the maximum pressure at hose connections.
To stay within these limits, very tall buildings are divided into pressure zones, each served by its own pump or by a pump feeding through a break. A typical arrangement stacks zones vertically, with each zone covering a band of floors so that no connection sees excessive pressure. Express risers, intermediate pump rooms, and gravity tanks are all tools for managing the pressure profile over height.
Pressure Regulation
Where the available pressure at a hose connection would exceed the safe operating limit for firefighting hose — generally taken as a maximum of about 175 psi at 1.5-inch connections and a higher limit at 2.5-inch connections — a pressure-regulating device is required. There are two important categories. A pressure-reducing valve actively limits both flowing and static (residual) pressure to a set value and must be field-adjusted and tested. A simpler pressure-restricting device limits flowing pressure only and does nothing at no-flow.
Pressure-regulating valves have a troubled history: improperly set valves have contributed to fireground failures because firefighters could not get adequate pressure. NFPA therefore requires that these valves be set, tested, and verified to deliver the required residual pressure and flow, and that they be flow-tested at acceptance and periodically thereafter.
Wet, Dry, and Combined Systems
- Automatic wet standpipes are filled with water and connected to a supply that meets the demand immediately — the standard for occupied buildings.
- Automatic dry and semiautomatic dry systems hold air or are empty until activated, used in unheated structures or parking garages where freezing is a concern.
- Manual standpipes have no permanent adequate supply and rely on the fire department pumping into the fire department connection, used only in limited, fully sprinklered, low-rise situations.
A fire department connection is provided on essentially all standpipe systems, allowing apparatus to boost or supply the system from the street.
Design Checklist
- Select the class based on intended users — Class I for fire department, Class III for combined use.
- Provide hose connections in every required stairway so the entire floor is covered.
- Meet 100 psi residual at the most remote 2.5-inch connection while flowing 500 plus 250 gpm per additional riser.
- Zone tall buildings to keep pressures within limits and add pressure-regulating valves where pressure is excessive — then test them.