Introduction to Psychrometrics
Psychrometrics is the science of the thermodynamic properties of moist air — a mixture of dry air and water vapor. For HVAC engineers, mastering the psychrometric chart is as fundamental as understanding electrical circuits for an EE. Every HVAC process — cooling, heating, dehumidifying, humidifying, mixing return and outside air — can be plotted and analyzed on the psychrometric chart, providing instant visual insight into the energy content of air streams and the performance of HVAC equipment.
The psychrometric chart used by ASHRAE (and defined in ASHRAE Fundamentals Handbook Chapter 1) is valid at sea-level atmospheric pressure (29.921 in. Hg, or 14.696 psia). For projects at elevations above 2,500 feet, altitude-corrected charts or software (such as ASHRAE CoolTools or carrier Hourly Analysis Program with altitude input) must be used — air density decreases with altitude, directly affecting coil capacity and fan performance.
Key Psychrometric Properties and Chart Axes
The psychrometric chart has the following key properties plotted on its axes and as curved lines:
- Dry-bulb temperature (DBT): The horizontal axis. Temperature measured by an ordinary thermometer. The most familiar property, ranging from approximately -40°F to 120°F on a standard HVAC chart.
- Humidity ratio (W): The vertical axis. Mass of water vapor per unit mass of dry air, in grains per pound (gr/lb) or pounds per pound (lb/lb). Also called specific humidity or moisture content. Standard room design conditions: approximately 54–65 gr/lb (0.0077–0.0093 lb/lb).
- Relative humidity (RH): Curved lines sweeping from lower left to upper right. The ratio of actual water vapor pressure to saturation vapor pressure at the same temperature, expressed as a percentage. The 100% RH line is the saturation curve (left boundary of the chart).
- Wet-bulb temperature (WBT): Diagonal lines sloping down-right from the saturation curve. Measured by a thermometer with a wet wick — evaporative cooling brings the temperature to the wet-bulb value. Used in cooling tower design, evaporative cooling, and equipment rating conditions (e.g., ARI rating: 80°F DB / 67°F WB entering air).
- Dew-point temperature (DPT): Read by drawing a horizontal line left from any state point to the saturation curve. The temperature at which air must be cooled at constant pressure for condensation to begin. Critical for preventing condensation on building surfaces and chilled-water pipes.
- Specific enthalpy (h): Lines parallel to wet-bulb lines, in Btu/lb dry air. Total energy content of the air-moisture mixture. The difference in enthalpy between two state points equals the energy added or removed per pound of dry air in that process. Standard room air at 75°F / 50% RH has enthalpy of approximately 28.1 Btu/lb dry air.
- Specific volume (v): Nearly vertical lines in cubic feet per pound of dry air. At design room conditions (75°F, 50% RH), v ≈ 13.5 ft³/lb. Used to convert between airflow in CFM and mass flow rate in lb/min.
Plotting HVAC Processes on the Psychrometric Chart
Every fundamental HVAC process traces a specific path on the chart:
- Sensible heating (no moisture change): Horizontal line moving right. DBT increases; humidity ratio W remains constant; RH decreases. Example: duct heating coil or heat pump heating coil.
- Sensible cooling (above dew point): Horizontal line moving left, until the dew point is reached. DBT decreases; W constant; RH increases. Example: air cooled without condensation.
- Cooling and dehumidification: A process line curving down and to the left toward the saturation curve. DBT and W both decrease. This is the typical cooling coil process. The apparatus dew point (ADP) is where the process line intersects the saturation curve — the effective coil surface temperature. The coil bypass factor (BF) = (leaving air DBT - ADP) / (entering air DBT - ADP).
- Humidification at constant temperature (isothermal — steam injection): Vertical line moving upward. DBT constant; W and RH increase. Steam injection adds moisture with negligible temperature change.
- Evaporative cooling (adiabatic humidification): Line following a constant wet-bulb line downward to the left. DBT decreases and W increases at constant enthalpy. Used in evaporative coolers in dry climates.
- Mixing of two airstreams: A straight line between the state points of the two streams. The mixed state point divides the line in inverse proportion to the mass flow rates of the two streams. Example: mixing OA and return air in an AHU economizer.
Sensible Heat Ratio and Equipment Selection
The Sensible Heat Ratio (SHR) is the ratio of sensible cooling load to total (sensible + latent) cooling load. SHR is plotted on the psychrometric chart as the slope of the process line from room design conditions to the apparatus dew point. SHR drives coil selection:
- High SHR (0.90–0.95): Dry climates, low latent load — less rows or higher leaving air temperature acceptable.
- Medium SHR (0.75–0.85): Typical commercial applications in mixed climates.
- Low SHR (0.60–0.70): Humid climates, spaces with high occupant density, or lab/clean room applications requiring strict humidity control. Requires deeper coils, lower leaving air temperatures, and often reheat.
The ASHRAE Handbook of Fundamentals provides psychrometric property tables and equations for detailed manual calculations. For daily practice, psychrometric software such as the ASHRAE Psychrometric Analysis CD, Carrier HAP, or free online calculators provide instant chart plotting and property lookup.
Altitude and Non-Standard Conditions
At elevations above sea level, atmospheric pressure decreases — approximately 1 in. Hg per 1,000 feet of elevation. Key effects on HVAC system design:
- Air density decreases: the same CFM carries less mass (lb/min) of air, reducing coil heat transfer and requiring more airflow (higher CFM) to deliver the same Btu/h.
- Fan performance derate: centrifugal fans produce less static pressure and less mass flow at altitude. The fan must be re-rated at altitude conditions — AMCA 99-0086 provides correction factors.
- DX equipment derates: refrigerant condensing conditions change at altitude because the condenser must reject heat to lower-density air. Always check manufacturer altitude derating data for rooftop units in Denver, Albuquerque, or other high-altitude cities.
- Evaporative cooling becomes more effective at altitude because low humidity and lower air density allow more evaporation per unit volume of airflow.