← HVAC Systems Studio
💨

CFM Airflow Calculator

Supply Airflow · ASHRAE 62.1 OA · BTU/hr to CFM

When to use: Use to determine the required supply airflow (CFM) for a zone based on its cooling or heating load. The formula CFM = BTU/hr ÷ (1.08 × ΔT) converts load to airflow, where ΔT is the temperature difference between supply air and room setpoint (typically 15–25°F). Also calculates the minimum outdoor air required per ASHRAE 62.1 based on occupancy and floor area.

Zone Parameters
BTU/hr
Cooling: 15–25°F
°F
ft²
people
Required Supply Airflow
1,667
CFM
Results
Supply Airflow (load-based)1,667 CFM
Min. Outdoor Air (ASHRAE 62.1)80 CFM
Equivalent Cooling Load3.0 tons
CFM per Ton556 CFM/ton
Temperature Differential20 °F
References
CFM = BTU/hr ÷ (1.08 × ΔT)
ASHRAE 62.1 Table 6-1 – Ventilation rates
Typical: 350–450 CFM/ton for cooling
Supply air temp: 55°F cooling, 105–120°F heating