← Gallery

EMT Conduit Fill Calculation: Four 350 kcmil Conductors and a Bonding Wire

A cross-section of 2-1/2 in. EMT holding four 350 kcmil THHN conductors and a 4 AWG bonding conductor. Total conductor area of 2.1792 in² against a 5.858 in² conduit gives 37.2% fill, within the 40% limit, with the table and calculation shown.

More in Conductors, Branch Circuits & Voltage Drop