Monthly Facility Load Profile and Load Factor
A 30-day hourly load profile for a campus on a 34.5 kV bus: 120 MW connected, 99.2 MW peak, 74.3 MW average, 60.1 MW minimum, a 0.75 load factor and 53,496 MWh of energy for the month.