Power Factor Correction: 100 kW Load from 0.78 to 0.95

A 480 V bus with a 100 kW load at 0.78 power factor, corrected with a 50 kvar capacitor bank (about 47.4 kvar needed). Before-and-after power triangles show the power factor reaching 0.957 and the line current falling from 154.2 A to 125.7 A.