NFPA 1221 / IFC 510 Coverage Compliance Simulator

Simulate a 5×5 grid of test points on a building floor and evaluate NFPA 1221 Section 9.6 / IFC 510.4 coverage compliance. Adjust BDA parameters and per-zone penetration losses to reach 95% area coverage.

NFPA 1221 / IFC 510 — COMPLIANT
25/25 test points pass both inbound & outbound (need 24/25 = 95%)
100%
System Parameters
-80 dBm
65 dB
24 dBm
3 dB
3 dBi
Building Penetration Losses
8 dB
6 dB
Outbound Pass25/25 (100%)
Inbound Pass25/25 (100%)
Both Pass25/25 (100%)
Required≥24/25 (95%)
Test Point Grid — Outbound RSSI
-47dBm-43dBm-38dBm-43dBm-47dBm-43dBm-32dBm-28dBm-32dBm-43dBm-38dBm-28dBm-25dBm-28dBm-38dBm-43dBm-32dBm-28dBm-32dBm-43dBm-47dBm-43dBm-38dBm-43dBm-47dBm
25/25 test points passing100% coverage
≥ −70 dBm (Excellent)
−80 to −90 dBm (Acceptable)
−90 to −95 dBm (Minimum)
< −95 dBm (Fail)
NFPA 1221 Section 9.6.3 / IFC 510.4.1.1: In-building coverage systems shall provide a minimum signal level of −95 dBm (inbound and outbound) throughout 95% of the building's floor area. Critical areas (stairwells, elevators, basements) typically require 100% coverage — test those separately.