Why Is an Electric Motor Overheating?
The common causes of motor overheating (overload, voltage problems, poor cooling, duty, drives and bearings), what to check for each, and a worked loss calculation.
Electrical & Power · Last reviewed
Motor heat comes from the motor's own losses. When the heat made is more than the heat the motor can shed, the temperature climbs. So the question is always one of two things: is the motor making more heat than it should, or is it losing less heat than it should?
Touch is not a measurement. A motor that is too hot to hold can still be inside its rating, and one that feels warm can be over it. Compare measured temperature with the nameplate insulation class and ambient rating. Measurements on energized equipment belong with qualified personnel following lockout/tagout and site procedures.
Related tools and labs
Calculators, labs and simulators are part of the All-Access Pass.
More troubleshooting
- Why Does a Circuit Breaker Keep Tripping?
- Why Does a VFD Trip on Overcurrent or Overvoltage?
- Why Is a Transformer Humming Loudly or Running Hot?
- Why Does a GFCI Keep Tripping?
- Why Is a Pump Delivering Low Flow or Making Noise?
- Why Is an Air Conditioner Not Cooling Enough?
- Why Is a 4-20 mA Loop Reading Wrong or Stuck?
- Why Does a PLC Output Not Turn On the Field Device?
Questions
What temperature is too hot?
It depends on the insulation class, the ambient rating and the service factor on the nameplate, and on how the temperature is measured. Use the manufacturer data, not a single number.
Can a motor overheat while drawing normal current?
Yes. Blocked cooling, high ambient, low-speed operation on a drive or too many starts can overheat a motor with normal running current.
Is a hot bearing the same as a hot winding?
No. Heat at one bearing end points to lubrication, alignment or load problems. Heat across the whole frame points to electrical or cooling causes.
How do I measure voltage unbalance?
Measure the three phase-to-phase voltages at the motor terminals with the motor running. Divide the largest deviation from the average by the average, and multiply by 100.
What are the common insulation classes?
Class B (130 °C), class F (155 °C) and class H (180 °C) are the common maximum operating temperatures for motor winding insulation. The nameplate gives the class and the allowed temperature rise.
Is the service factor a reason to run a motor overloaded?
No. The service factor is a reserve for occasional overload. Running continuously in the service-factor range shortens insulation life.
Educational material. Examples use simplified, hypothetical inputs and are not a design, a construction document or professional engineering advice. Confirm requirements with the codes and standards adopted where the work is built and with a licensed engineer.