Case study

The August 2003 Northeast Blackout: Four Groups of Causes

A blackout affecting about 50 million people began in Ohio. The U.S.-Canada Task Force found four groups of causes: inadequate system studies, poor situational awareness, tree growth near lines, and weak reliability coordination.

Electrical & Power · Last reviewed

What happened

On August 14, 2003, large parts of the Midwest and Northeast United States and Ontario, Canada lost power. The outage affected an area with an estimated 50 million people and 61,800 megawatts of electric load. It began a few minutes after 4:00 p.m. Eastern Daylight Time, and power was not restored for four days in some parts of the United States. Parts of Ontario had rolling blackouts for more than a week.

What the Task Force found

The U.S.-Canada Power System Outage Task Force identified four groups of causes for the start of the blackout in Ohio:

  1. FirstEnergy and its reliability council failed to assess and understand the inadequacies of the FirstEnergy system, particularly voltage instability and the vulnerability of the Cleveland-Akron area, and FirstEnergy did not operate its system with appropriate voltage criteria.
  2. FirstEnergy had inadequate situational awareness. It did not recognize or understand the deteriorating condition of its system, in part because of problems with its monitoring and alarm tools and the procedures around them.
  3. FirstEnergy failed to manage adequately tree growth in its transmission rights-of-way. This was the common cause of the outage of three 345-kV lines and one 138-kV line.
  4. The reliability organizations of the interconnected grid failed to provide effective real-time diagnostic support.

The report notes that insufficient reactive power was an issue but was not a cause in itself: deficiencies in corporate policies, adherence to industry policies and management of reactive power and voltage caused the blackout.

Apply the lesson

  • If the main monitoring tool fails silently, how would an operator know? What is the backup?
  • After a repair, how do you test that an alarm or monitoring function actually works again?
  • Is vegetation clearance for lines on a schedule with records, and who audits it?
  • Does your contingency analysis cover the "next" failure while the system is already stressed?

Engineering lesson: a large cascading failure usually starts with several small gaps, each one ordinary by itself. Watching, testing the monitors, and studying the next contingency close the gaps.

What the Task Force recommended

The final report includes 46 recommendations, in its Chapter 10. In its letter to the President and the Prime Minister, the Task Force wrote that the blackout could have been prevented, and that, first and foremost, compliance with reliability rules must be made mandatory with substantial penalties for non-compliance. It also wrote that failure to implement the recommendations would threaten the reliability of the electricity supply that is critical to the economic, energy and national security of both countries.

Related tools and labs

Calculators, labs and simulators are part of the All-Access Pass.

More case studies

Questions

Did a single piece of equipment cause it?

The Task Force describes four groups of causes involving practices, equipment and human decisions. It does not point to one failure alone.

Where can I read the report?

The Final Report of the U.S.-Canada Power System Outage Task Force is hosted by the U.S. Department of Energy, linked below.

How many recommendations were made?

The report's Chapter 10 includes a total of 46 recommendations.

What did the Task Force say should come first?

That compliance with reliability rules must be made mandatory, with substantial penalties for non-compliance.

Sources

Educational material. Examples use simplified, hypothetical inputs and are not a design, a construction document or professional engineering advice. Confirm requirements with the codes and standards adopted where the work is built and with a licensed engineer.

← All case studies