🔋 NFPA 72 §10.6.7 Calculator

Battery Backup Calculation Worksheet

Size the standby battery for any fire alarm system per NFPA 72 §10.6.7 — 24-hour standby load plus 5-minute full alarm load, with derating factor applied.

Device Load Schedule

Device DescriptionStandby (mA)Alarm (mA)Qty
TOTAL SYSTEM LOAD292 mA1216 mA

System Parameters

Calculation Results

Standby Load (24h × 292mA)
7.00 Ah
NFPA 72 §10.6.7.2
Alarm Load (5min × 1216mA)
0.101 Ah
NFPA 72 §10.6.7.3
Raw Capacity Required
7.10 Ah
Standby + Alarm
After 20% Derating Factor
8.87 Ah
NFPA 72 §10.6.7.4
MINIMUM BATTERY SIZE
9.0 Ah
at 24VDC · Rounded up to nearest 0.5 Ah
⚠️ Always verify battery sizing with the FACP manufacturer's documentation. Actual standby and alarm currents must come from the panel's Installation and Maintenance manual.
NFPA 72 Formula
C = (Istby × Tstby)
    + (Ialm × Talm)
Crated = C ÷ (1 − D)
C = raw Ah · D = derating