What actually happens the instant a single wire fault occurs — and why one wiring topology loses devices while the other doesn't.
Every NFPA 72 initiating device circuit, signaling line circuit, or notification appliance circuit is wired one of two ways. Class B runs out to each device and back to the panel along the same physical path — a simple "home run." Class A runs out to the last device and then keeps going, via a second, separately-routed conductor, all the way back to the panel — entering through its own dedicated connection and forming a genuine loop.
On paper that sounds like a minor wiring detail. In practice, it's the difference between a system that keeps working through a single break and one that doesn't. The two diagrams below show the identical fault — one break, in the identical location — wired each way.