This is a general awareness overview, not a substitute for a licensed fire protection or mechanical engineer's smoke control system design. Real smoke control system design — including fan CFM sizing — must be based on the current NFPA 92 standard, and the completed system often requires commissioning and acceptance testing per NFPA 92 and the local Authority Having Jurisdiction (AHJ) before it can be placed in service. Never rely on this page to size, install, or accept a smoke control system.
These two figures are consistently published across many independent secondary sources describing NFPA 92 pressurization design, making them lower-risk general reference values than the standard's detailed algebraic fan-sizing equations (discussed below).
NFPA 92's actual algebraic equations for sizing pressurization fan airflow live in the standard's annexes. Hand-calculating fan CFM from those equations is only valid for a simplified case — buildings with uniform floor area and all doors assumed closed. Real buildings frequently violate that assumption (varying floor plate sizes, stack effect, open-door scenarios during evacuation, elevator lobby interactions), which is why many real projects use computer modeling — for example, NIST's CONTAM multizone airflow software — to size and verify the system under realistic conditions.