← Smart Buildings Studio
🔥

DDC Panel Heat Dissipation

NEMA · UL 508A · Enclosure Thermal Load

When to use: Use when sizing the thermal management of a DDC control panel or BAS enclosure. Sum the heat dissipated by controllers, I/O modules, and the power supply/transformer, then compare it against the enclosure's passive free-convection capacity. A sealed metal box sheds roughly 0.5 W per ft² per °F of internal-to-ambient temperature difference. If the heat load exceeds what the surface can passively shed, a filtered fan or panel A/C is required to keep internal temperatures within the rating of the electronics.

Panel Heat Sources
#
default 8
W
#
default 3
W
default 25
W
ft²
default 20
°F
Heat Balance
75.0
Heat load (W)
200.0
Passive shed (W)
✓ PASSIVE COOLING OK
75.0
Total Heat Load (W)
Results
Total Heat75.0 W
Total Heat256 BTU/hr
Passive Dissipation200.0 W
Predicted Temp Rise7.5 °F
Active Cooling RequiredNone
RecommendationSealed enclosure OK
References
NEMA / UL 508A enclosure thermal sizing
Q(BTU/hr) = Watts × 3.412
Free-convection ≈ 0.5 W/(ft²·°F)
Active cooling when load > passive dissipation