Preaction vs Dry Pipe Sprinkler Systems
Dry pipe systems hold air and open on a sprinkler. Preaction systems also need detection first. Compare sequence, freezing and accidental discharge.
Fire Protection · Last reviewed
Short answer: use a dry pipe system to protect spaces that can freeze. Use a preaction system where an accidental discharge would be very costly, such as data centers, archives and museums. A preaction system adds fire detection and a more complex control, and it may also be used in freezing spaces.
| Dry pipe | Preaction | |
|---|---|---|
| Pipe contents | Compressed air or nitrogen | Air at low pressure or unpressurized, depending on the type |
| Operating sequence | A sprinkler opens, the air escapes, the valve trips and water flows to the open sprinkler | Detection opens the valve (single interlock), or detection and an opened sprinkler are both needed (double interlock) |
| Detection interface | None needed, although supervisory pressure is monitored | A separate detection system (smoke, heat or flame) controls the valve |
| Water delivery delay | Water must displace the air in the pipe, which takes time | With single interlock, water is in the pipe before heat opens a sprinkler. With double interlock, a delay is possible |
| Freezing exposure | Suitable, because the pipes hold no water | Suitable, with the same attention to the water in the valve and risers |
| Accidental discharge | A damaged sprinkler lets air out and can trip the valve | Protected: a damaged sprinkler alone does not release water in a double interlock system |
| Complexity | Moderate: air supply and maintenance | Higher: detection, releasing panel and valve control |
| Maintenance | Air pressure, leaks, drains, valve trip tests | All of the dry pipe needs plus the detection and the releasing control tests |
| Cost | Moderate | Higher |
Related tools and labs
Calculators, labs and simulators are part of the All-Access Pass.
More comparisons
- Wet vs Dry Pipe Sprinkler Systems
- Conventional vs Addressable Fire Alarm Systems
- Photoelectric vs Ionization Smoke Detection
- Smoke Detectors vs Heat Detectors: How to Choose
- Spot Smoke Detection vs Aspirating Smoke Detection
- VFD vs Soft Starter: Which One for an AC Induction Motor?
- Star-Delta vs Direct-on-Line Motor Starting
- Copper vs Aluminum Feeders: How to Choose
Questions
What is a double interlock?
A preaction system where both a detector signal and an open sprinkler (loss of air pressure) are needed before water enters the pipe. It lowers the chance of an accidental discharge and adds delay.
Can a preaction system be used in a freezing space?
Yes, if it is designed for it. Check the valve and riser protection and the code.