Star-Delta vs Direct-on-Line Motor Starting
Star-delta starting cuts line current to about one third and torque to about one third. Compare it with direct-on-line starting and know when each fits.
Electrical & Power · Last reviewed
Short answer: direct-on-line is the simplest and gives full starting torque, but draws the highest inrush. Star-delta cuts the inrush and the torque to about one third each, and only suits motors that start with a light load.
| Direct-on-line (DOL) | Star-delta | |
|---|---|---|
| How it starts | Full voltage across the windings immediately | Starts with windings in star, then switches to delta |
| Starting current | Typically about 6 to 8 times full-load current | About one third of the DOL value |
| Starting torque | Full (roughly 1.5 to 2.5 times full-load torque, depends on the motor) | About one third of the DOL value |
| Motor requirement | Any standard motor | Six terminals brought out, and a winding rated for the line voltage in delta |
| Equipment | One contactor and overload | Three contactors, a timer and an overload |
| Switchover | None | Brief current and torque transient at the star-to-delta change |
| Best for | Small motors and strong supplies | Larger motors starting unloaded or lightly loaded (fans, some pumps, machine tools) |
Related tools and labs
Calculators, labs and simulators are part of the All-Access Pass.
More comparisons
- VFD vs Soft Starter: Which One for an AC Induction Motor?
- Copper vs Aluminum Feeders: How to Choose
- MCCB vs ACB: Molded-Case or Air Circuit Breaker?
- Dry-Type vs Liquid-Filled Transformers
- VAV vs CAV: Variable or Constant Air Volume Systems
- Air-Cooled vs Water-Cooled Chillers
- Centrifugal vs Positive-Displacement Pumps
- PLC vs DCS: Which Control System for the Plant?
Questions
Why does star connection reduce current to one third?
In star each winding sees the line voltage divided by √3. Winding current falls by √3 and the line current by a further √3 against delta, so the line current is about one third.
Is star-delta still common?
Yes, though soft starters and VFDs have replaced it in many new installations because they avoid the switchover transient.
Can I use star-delta on any motor?
No. The motor must be rated for delta operation at the supply voltage, with all six leads brought out.
What causes the second current peak?
When the starter switches from star to delta, the motor is briefly disconnected and then reconnected at full voltage. If it has not reached near full speed by then, the second peak can approach the DOL value.
How is the star time set?
Set it long enough for the motor to reach close to full speed in star, but short enough that it does not overheat. Typical values are a few seconds up to about 15 seconds for large fans.
Educational material. Examples use simplified, hypothetical inputs and are not a design, a construction document or professional engineering advice. Confirm requirements with the codes and standards adopted where the work is built and with a licensed engineer.