EQUIPMENT & SYSTEM TOURS

Inside a Liquid-Cooling System / CDU

Follow heat from server cold plates through an isolated two-loop coolant distribution system.

Published and reviewed

How a liquid-to-liquid CDU transfers heat

A coolant distribution unit isolates the technology cooling system (TCS) from the facility water system (FWS). Server cold plates transfer chip heat to technology coolant. That coolant passes through one side of a heat exchanger; facility water receives the heat on the other side. The fluids remain separate. This CDU does not contain a refrigeration cycle and does not itself guarantee low annual water use.

Trace two complete circuits

Facility supply → exchanger facility channels → warmer facility return → external heat-rejection plant. Separately: exchanger technology outlet → circulation pumps and filter → rack supply manifold → cold plates → rack return manifold → exchanger technology inlet. The representative rack retains other components that may still need air cooling.

Worked steady-state heat balance

Assume 100 kW of chip heat, pure water with specific heat 4.18 kJ/(kg·K), density 1,000 kg/m³ and technology coolant warming from 25°C to 35°C. Required mass flow is Q ÷ (cp × ΔT) = 100 ÷ (4.18 × 10) = 2.392 kg/s, approximately 8.61 m³/h. With the same assumed fluid/flow on the facility side, 20°C supply would return at 30°C. The cold-end approach is 25 − 20 = 5 K. Pump heat and ambient losses are neglected in this example.

The energy balance does not size an exchanger or establish a chip temperature. Exchanger UA, approach at both ends, pressure loss, fluid properties and manufacturer performance data must support the selected operating point. Glycol mixtures require appropriate temperature-dependent properties; the pure-water example cannot be applied unchanged.

Pumps, filtration and monitoring

Parallel pump branches, isolation valves, a filter and expansion vessel show distinct fluid-management functions. Two installed pumps alone do not establish N+1 availability: capacity, power, controls, valves and common failures matter. Temperature, flow, pressure and leak sensing support observation and protection. The model shows those locations without simulating a control sequence or reporting operating measurements.

Choose the next study

Compare heat load and cooling flow · Compare site water and electricity-related water · Direct-to-chip versus immersion

Inspect the parts, then follow their connections

Start with the complete equipment, then follow eight short explanations with guided close-up views. Pause and resume at the same point, or select any component, orbit and zoom. Cutaway and exploded views reveal parts that the enclosure would otherwise hide.

About this model and references

Representative liquid-to-liquid CDU and four-server rack. Fluids, dimensions, flow and control responses are illustrative; no refrigerating cycle, equipment rating, validated redundancy or operating procedure is modeled.

These are original representative models and teaching overlays, not manufacturer replicas, validated operating simulations or maintenance procedures.

AI Data Centers Studio · HVAC Studio · Mechanical Studio · Facility Tours