Comparison

RTD vs Thermocouple: Which Temperature Sensor Fits?

RTDs are accurate and stable. Thermocouples reach very high temperatures and tolerate vibration. Compare range, accuracy, response and wiring.

Controls & Instrumentation · Last reviewed

Short answer: choose an RTD for accurate, stable measurement up to about 600 °C, such as in HVAC, food and process work. Choose a thermocouple for very high temperatures, fast response, rugged or vibrating installations and low cost.

RTD (for example Pt100)Thermocouple (for example type K)
Temperature rangeAbout −200 to 600 °C for common typesAbout −200 to over 1,200 °C for type K, and higher for other types
AccuracyBetter. Class A is about ±(0.15 + 0.002 × t) °C, which is ±0.35 °C at 100 °CTypical standard limits are about ±1.5 to ±2.2 °C or a fraction of a percent of the reading, which is looser than an RTD
Stability and driftVery stable over timeCan drift as the wires age, especially at high temperature
Response timeSlower, with a larger elementFast, especially with a small junction
OutputResistance, about 0.385 Ω/°C for Pt100, which needs an excitation currentA small voltage, about 0.04 mV/°C for type K, which needs cold-junction compensation
Wiring2, 3 or 4 wires, with copper cable. Lead resistance matters for 2-wireThermocouple extension wire of the right type, with correct polarity
Vibration and shockMore fragile elementRugged
CostHigher sensor costLower sensor cost, though the extension wire can cost more
Typical usesHVAC, pharmaceutical, food, laboratory, process controlFurnaces, exhausts, kilns, engines and high-temperature processes

How to choose

  1. Check the temperature range, including upsets. Above about 600 °C the choice is usually a thermocouple.
  2. Decide how accurate and stable the reading must be. A control or billing measurement favors an RTD.
  3. Check the response time needed, and the effect of any thermowell.
  4. Look at vibration, shock and the installation conditions.
  5. Check the input module: it must match the sensor type and wiring. Plan wiring and the cost of cable.

Common mistakes

  • Using a 2-wire RTD with long leads, which adds an offset (3 Ω of lead resistance is about 7.8 °C on a Pt100).
  • Using ordinary copper wire for a thermocouple.
  • Configuring the input for the wrong sensor type.
  • Choosing an RTD for a very hot, vibrating location where it will fail.

Related tools and labs

Calculators, labs and simulators are part of the All-Access Pass.

More comparisons

Questions

Can I replace a thermocouple with an RTD?

Only if the range allows it and the input module is changed to suit. The wiring and the transmitter or input type must match.

Why does a thermocouple need cold-junction compensation?

The voltage depends on the difference between the hot and the cold junctions, so the instrument has to measure the terminal temperature and correct for it.

Educational material. Examples use simplified, hypothetical inputs and are not a design, a construction document or professional engineering advice. Confirm requirements with the codes and standards adopted where the work is built and with a licensed engineer.