Challenge: Can You Add Two Sprinkler Pressures?
An engineer adds the pressures of two parallel sprinklers to get 14 psi. Find the mistake and how flow and pressure behave at a junction.
Fire Protection · Last reviewed
Two identical sprinklers (K = 5.6 gpm/psi^½) are connected in parallel to one junction, and each needs 7.0 psi to discharge. An engineer calculates the supply requirement at the junction like this:
- Each sprinkler: K = 5.6 gpm/psi^½, needs 7.0 psi at its inlet.
- The two sprinklers branch from the same junction through short pipes with negligible friction.
Your task: find the mistakes, calculate the correct pressure and total flow at the junction, and say what changes if each short pipe loses 0.5 psi to friction.
Related tools and labs
Calculators, labs and simulators are part of the All-Access Pass.
More worked problems
- Sprinkler Flow from K-Factor and Pressure
- Fire Alarm Control Panel Battery Calculation
- Fire Alarm NAC Voltage Drop with Distributed Devices
- Sprinkler Branch Line: Work Back from the Remote Head
- Fire Pump Duty: Flow, Pressure and Elevation
- Fire-Water Storage: Demand, Duration and Usable Volume
- Size the Branch Circuit for a 40 hp, 460 V Motor
- Voltage Drop on a 240 V Single-Phase Feeder
Questions
Where do pressures add?
Along a single pipe path in series: the supply pressure must cover the pressure at the end plus the friction and elevation losses along the path.
What if the two sprinklers need different pressures?
The junction pressure must be at least the higher requirement. The sprinkler with the lower requirement then discharges more than its minimum flow.
Educational material. Examples use simplified, hypothetical inputs and are not a design, a construction document or professional engineering advice. Confirm requirements with the codes and standards adopted where the work is built and with a licensed engineer.