Size the Branch Circuit for a 40 hp, 460 V Motor
Conductor size, breaker, overload setting and disconnect rating for a 40 hp, 460 V, 3-phase induction motor, using NEC Article 430 tables.
Electrical & Power · Last reviewed
Given
40 hp induction motor, 460 V, 3-phase, copper conductors, 75 °C terminations. Nameplate full-load current 48 A, service factor 1.15.
Find
Conductor size, short-circuit and ground-fault protection, overload setting, and minimum disconnect rating.
Solution
Related tools and labs
Calculators, labs and simulators are part of the All-Access Pass.
More worked problems
- Voltage Drop on a 240 V Single-Phase Feeder
- Office Lighting Load: Connected Power and Current
- Challenge: The Current That Looks Too High
- Size a Three-Phase Transformer for a Mixed Load
- Power Factor Correction: How Many kvar of Capacitors?
- Short-Circuit Current at a Transformer Secondary
- Pump Head, Shaft Power and Motor Size
- Sensible Cooling Capacity from Airflow and Temperature Difference
Questions
Why does the conductor use the table current and the overload use the nameplate?
The conductor and the short-circuit device are sized from the standard table so the circuit works with any motor of that rating. The overload device protects this particular motor, so it follows its nameplate.
Is 150 A always allowed?
Not always. It is the maximum for an inverse-time breaker on this example. Other device types and motor designs have different limits in Table 430.52.
What changes at a different voltage?
The table full-load current changes with voltage, and every number after it changes with it.
What is the difference between table full-load current and nameplate current?
The table value is a standard number for a motor of that horsepower and voltage, used to size conductors, the short-circuit device and the disconnect. The nameplate value is the actual rated current of the motor you have, used for the overload device.
Does a variable frequency drive change the sizing?
Yes. Conductors that supply a drive are sized from the drive's rated input current, and the conductors from the drive to the motor are sized from the motor full-load current. Follow the drive manual and the NEC articles that cover adjustable-speed drives (430.122 and 430.22).
Why can a termination limit the conductor size?
Equipment terminations on smaller circuits are commonly rated for the 60 °C ampacity unless the equipment is marked for 75 °C. Check NEC 110.14(C) and the markings on the equipment before using the 75 °C column.
Educational material. Examples use simplified, hypothetical inputs and are not a design, a construction document or professional engineering advice. Confirm requirements with the codes and standards adopted where the work is built and with a licensed engineer.