Differential-Pressure Flow: Why 50% Signal Is Not 50% Flow
Convert a 12 mA signal from a linear differential-pressure transmitter into flow with the square-root law, and compare a flow-linear output.
Controls & Instrumentation · Last reviewed
Given
An orifice plate measures a flow that is 0 to 500 gpm. The differential-pressure (DP) transmitter is ranged 0 to 100 inH₂O for 4 to 20 mA. The flow through an orifice varies with the square root of the DP, so 100 inH₂O corresponds to 500 gpm.
Find
The flow when the signal is 12 mA, the signal at 50% flow, and the result when the transmitter itself extracts the square root.
Solution
Related tools and labs
Calculators, labs and simulators are part of the All-Access Pass.
More worked problems
- 4-20 mA Signal Scaling for a Pressure Transmitter
- Control Valve Sizing: Calculate Cv for a Water Line
- Hydrostatic Level Measurement: Pressure to Tank Level
- First-Order Sensor Response: Time Constant and Settling
- PLC Analog Input: Raw Counts to Engineering Units
- Measurement Uncertainty: Combining Independent Inputs
- Size the Branch Circuit for a 40 hp, 460 V Motor
- Voltage Drop on a 240 V Single-Phase Feeder
Questions
Why is flow proportional to the square root of DP?
The DP across an orifice or venturi comes from the change in velocity head, which scales with the square of the velocity. So velocity, and flow, scales with the square root of DP.
How do I know how my transmitter is configured?
Check the transmitter configuration for the output mode (linear or square root), the range and the units. Confirm in the loop documentation and the PLC scaling.
Does the turndown limit apply?
Yes. A DP flow meter loses accuracy at low flow, so the usable range is typically limited to about 10:1 or less.
Educational material. Examples use simplified, hypothetical inputs and are not a design, a construction document or professional engineering advice. Confirm requirements with the codes and standards adopted where the work is built and with a licensed engineer.