4-20 mA Signal Scaling for a Pressure Transmitter
Convert a 4-20 mA reading to engineering units for a 0 to 10 bar transmitter, and work backward to the expected current for a given pressure.
Controls & Instrumentation · Last reviewed
Given
A pressure transmitter is ranged 0 to 10 bar and outputs 4 to 20 mA (4 mA = 0 bar, 20 mA = 10 bar).
Find
The pressure for readings of 12 mA and 7.2 mA, and the current at 3.5 bar.
Solution
Related tools and labs
Calculators, labs and simulators are part of the All-Access Pass.
Questions
What is a two-wire transmitter?
A transmitter powered by the same two wires that carry the signal (loop-powered), usually from a 24 V DC supply.
What limits loop length?
The supply voltage must cover the transmitter minimum voltage plus the voltage drop across the loop resistance and the input resistor. A 250 ohm input resistor drops 1 to 5 V across the 4-20 mA range.
How do I turn the current into a voltage for an analog input?
A precision resistor across the input does it. A 250 ohm resistor turns 4 to 20 mA into 1 to 5 V. Many analog input cards have the resistor built in.
What current means a fault?
Many devices follow the NAMUR NE43 recommendation: the valid measuring range is about 3.8 to 20.5 mA, and a signal at or below 3.6 mA or at or above 21 mA indicates a failure.
Why is 4-20 mA used and not a voltage signal?
A current signal is not affected by wire resistance, so it travels long distances with little error, and the live zero lets the system detect a broken wire.
Educational material. Examples use simplified, hypothetical inputs and are not a design, a construction document or professional engineering advice. Confirm requirements with the codes and standards adopted where the work is built and with a licensed engineer.