Fan Laws: What Changes When Speed Drops?
Estimate airflow, pressure and shaft power when a fan slows from 1,200 to 900 rpm, and why the cube law does not predict electricity savings.
Mechanical, HVAC & Fluids · Last reviewed
Given
A fan delivers 12,000 CFM at 1.5 in. w.g. total pressure and 6.0 bhp at 1,200 rpm. The speed is reduced to 900 rpm. Assume the same fan, the same air density, and a duct system whose resistance is a pure friction curve (pressure proportional to flow squared).
Find
The new airflow, pressure and shaft power, and whether the result predicts the change in electricity use.
Solution
Related tools and labs
Calculators, labs and simulators are part of the All-Access Pass.
More worked problems
- Pump Head, Shaft Power and Motor Size
- Sensible Cooling Capacity from Airflow and Temperature Difference
- Chilled-Water Flow Rate from Load and Delta-T
- Counterflow Heat Exchanger: Log-Mean Temperature Difference
- Total Cooling Load from Air Enthalpy
- Pipe Pressure Loss: Straight Pipe Plus Fittings
- Size the Branch Circuit for a 40 hp, 460 V Motor
- Voltage Drop on a 240 V Single-Phase Feeder
Questions
Does a 25% speed reduction save 58% of the energy?
Only in the ideal case. The shaft power falls by 58%, but electricity falls by somewhat less, and a system with fixed static pressure falls by much less.
Do the fan laws work for pumps?
The same affinity laws apply to centrifugal pumps, with the same limits: the system curve must pass through the origin, so a pump working against static head does not follow the cube law.
How do I get real values?
Use the fan curve at the new speed and the system curve, and find the intersection, then use the manufacturer power data.
Educational material. Examples use simplified, hypothetical inputs and are not a design, a construction document or professional engineering advice. Confirm requirements with the codes and standards adopted where the work is built and with a licensed engineer.