Total Cooling Load from Air Enthalpy
Find total cooling capacity from dry-air mass flow and enthalpy change, then the latent capacity and sensible heat ratio against a 30 kW sensible load.
Mechanical, HVAC & Fluids · Last reviewed
Given
A cooling coil handles 2.5 kg/s of dry air. Read from a psychrometric chart, the entering air has an enthalpy of 55.0 kJ/kg of dry air (roughly 27 °C and 50% relative humidity) and the leaving air 38.0 kJ/kg (about 13.5 °C, close to saturated). The sensible part of the load is 30.0 kW.
Find
The total cooling capacity, the latent capacity, the sensible heat ratio and the capacity in tons of refrigeration.
Solution
Related tools and labs
Calculators, labs and simulators are part of the All-Access Pass.
More worked problems
- Pump Head, Shaft Power and Motor Size
- Sensible Cooling Capacity from Airflow and Temperature Difference
- Chilled-Water Flow Rate from Load and Delta-T
- Counterflow Heat Exchanger: Log-Mean Temperature Difference
- Fan Laws: What Changes When Speed Drops?
- Pipe Pressure Loss: Straight Pipe Plus Fittings
- Size the Branch Circuit for a 40 hp, 460 V Motor
- Voltage Drop on a 240 V Single-Phase Feeder
Questions
What is a normal sensible heat ratio?
Many comfort-cooling applications run between about 0.7 and 0.9. A low value means a large latent load, such as high outdoor-air ventilation or a crowd of people.
Where do the enthalpies come from?
From a psychrometric chart or equations, using the dry-bulb temperature and humidity of the entering and leaving air.
What if the coil does not dehumidify?
If the coil surface stays above the dew point of the air, there is no condensation, the latent capacity is zero and the SHR is 1.0.