Sensible Cooling Capacity from Airflow and Temperature Difference
Use Q = 1.08 × CFM × ΔT to find the sensible cooling delivered by 2,000 CFM of air at a 20 °F temperature drop, and convert it to tons.
Mechanical, HVAC & Fluids · Last reviewed
Given
An air handler delivers 2,000 CFM of supply air to a room. The supply air is 20 °F colder than the room air. Standard air at sea level.
Find
The sensible cooling capacity in Btu/h and in tons of refrigeration.
Solution
Related tools and labs
Calculators, labs and simulators are part of the All-Access Pass.
More worked problems
- Pump Head, Shaft Power and Motor Size
- Chilled-Water Flow Rate from Load and Delta-T
- Counterflow Heat Exchanger: Log-Mean Temperature Difference
- Size the Branch Circuit for a 40 hp, 460 V Motor
- Voltage Drop on a 240 V Single-Phase Feeder
- Office Lighting Load: Connected Power and Current
- Challenge: The Current That Looks Too High
Questions
How do I include latent cooling?
The latent load uses 0.68 × CFM × Δgrains of moisture per pound of dry air (Btu/h, standard air), or an enthalpy calculation. Total capacity is sensible plus latent.
How do I find the airflow I need?
Rearrange: CFM = Q ÷ (1.08 × ΔT). A 43,200 Btu/h sensible load at ΔT = 20 °F needs 2,000 CFM.
Why is the factor 1.08 and not 1?
It combines the density of air, its specific heat and the 60 minutes in an hour. See the explanation above for how it is built.
How does altitude change the calculation?
Thinner air carries less heat per cubic foot, so the factor is lower and more airflow is needed for the same capacity. Correct it with the density ratio at the site elevation.
What is the difference between sensible, latent and total cooling?
Sensible cooling lowers the air temperature. Latent cooling removes moisture. Total cooling is the sum of the two and is what the equipment capacity rating describes.