Pipe Pressure Loss: Straight Pipe Plus Fittings
Use Darcy–Weisbach and fitting K values to find the water pressure loss in a short DN100 line and see whether pipe or fittings dominate.
Mechanical, HVAC & Fluids · Last reviewed
Given
Water (density 998 kg/m³) flows at 10 L/s through a 4 in. Schedule 40 steel line with an inside diameter of 102.3 mm. Straight length 25 m. Supplied Darcy friction factor f = 0.022. Fittings: 4 elbows with K = 0.9 each, one open gate valve K = 0.2, one strainer K = 3.0, a pipe entrance K = 0.5 and an exit K = 1.0.
Find
The total pressure loss, and whether the straight pipe or the fittings contribute more.
Solution
Related tools and labs
Calculators, labs and simulators are part of the All-Access Pass.
More worked problems
- Pump Head, Shaft Power and Motor Size
- Sensible Cooling Capacity from Airflow and Temperature Difference
- Chilled-Water Flow Rate from Load and Delta-T
- Counterflow Heat Exchanger: Log-Mean Temperature Difference
- Total Cooling Load from Air Enthalpy
- Fan Laws: What Changes When Speed Drops?
- Size the Branch Circuit for a 40 hp, 460 V Motor
- Voltage Drop on a 240 V Single-Phase Feeder
Questions
Where does the friction factor come from?
From the Moody chart or the Colebrook equation, using the Reynolds number and the relative roughness of the pipe. Here it is supplied so that the focus stays on the method.
How is the loss converted to head?
Divide the pressure loss by ρg: 10,102 ÷ (998 × 9.81) = 1.03 m.
Does this include elevation change?
No. Elevation adds ρgΔz to the pressure budget separately.