Pump Cavitation Check: NPSH Available vs. Required
Calculate NPSH available for 60 °C water from an open tank at 1,500 m elevation and compare it with NPSH required plus a stated margin.
Mechanical, HVAC & Fluids · Last reviewed
Given
A pump draws water from an open tank at a site 1,500 m above sea level. The water surface is 1.2 m above the pump centerline, and the suction line losses at the design flow are 0.8 m. The water is at 60 °C, with a vapor pressure of 19.94 kPa and a density of 983.2 kg/m³. The manufacturer gives NPSH required = 4.5 m at the duty flow. For this exercise require NPSH available to exceed NPSH required by at least 1.0 m.
Find
NPSH available, and whether the pump is acceptable. Then repeat for 80 °C water.
Solution
Related tools and labs
Calculators, labs and simulators are part of the All-Access Pass.
More worked problems
- Pump Head, Shaft Power and Motor Size
- Sensible Cooling Capacity from Airflow and Temperature Difference
- Chilled-Water Flow Rate from Load and Delta-T
- Counterflow Heat Exchanger: Log-Mean Temperature Difference
- Total Cooling Load from Air Enthalpy
- Fan Laws: What Changes When Speed Drops?
- Size the Branch Circuit for a 40 hp, 460 V Motor
- Voltage Drop on a 240 V Single-Phase Feeder
Questions
What happens when NPSHa is too low?
Vapor bubbles form at the impeller inlet and collapse as the pressure recovers. That causes noise, vibration, loss of head and damage to the impeller over time.
Is a 1.0 m margin a standard?
No. It is an exercise value. Margins used in practice depend on the application, the pump type and the owner or standards requirements.
How can I raise NPSHa?
Raise the liquid level, shorten or enlarge the suction line, lower the liquid temperature, or lower the pump.