A step-by-step way to size a commercial battery energy storage system: kW vs kWh, duration, usable capacity, efficiency, degradation and use case, with a worked peak-shaving example using hypothetical numbers.
The Short Answer
A battery energy storage system is sized by two numbers: power in kilowatts or megawatts (how fast it can charge or discharge) and energy in kilowatt-hours or megawatt-hours (how much it can deliver). Duration is energy divided by power, so a 500 kW / 1,000 kWh system has a two-hour duration. The use case sets both numbers: power comes from the load or demand you must cover, and energy comes from how long you must cover it, adjusted for usable capacity, efficiency and the capacity lost over the system's life.
Step 1: Define the Use Case
- Peak shaving (demand charge reduction): power equals the amount of peak you want to cut. Energy equals the area of the load profile above the target threshold during the peak events.
- Backup power: power equals the critical load. Energy equals the critical load multiplied by the hours of backup required.
- Solar shifting or arbitrage: duration follows the length of the period you need to shift or the price spread you want to capture.
Step 2: Size the Power Rating
Find the maximum kW the battery must deliver or absorb, then compare it with the power conversion system (inverter) rating, which limits the battery's real output. The ratio of power to energy is the C-rate: a 1C system can discharge its full capacity in one hour, and a 0.5C system takes two hours. Higher C-rates stress the battery more and can reduce life.
Step 3: Size the Energy Rating
Start with the energy the load needs, then work back to nameplate capacity:
- Usable fraction: batteries are not discharged to zero. A system with a 90% usable fraction needs nameplate capacity equal to required energy divided by 0.9.
- Efficiency: round-trip efficiency (energy out divided by energy in) affects the energy you must buy to charge the battery. If the datasheet already states usable energy at the AC output, do not apply the efficiency loss a second time.
- Degradation: capacity falls over the years. If the project must meet its requirement at the end of its life, divide again by the expected end-of-life capacity fraction, or plan for augmentation, which means adding capacity later.
- Auxiliary loads and temperature: cooling, the battery management system and cold or hot conditions reduce the energy available to the load.
Worked Example (Hypothetical Numbers)
A facility has a peak demand of 1,200 kW and wants to hold it to 900 kW. On a peak day the load is 300 kW above the threshold for one hour, 200 kW above for one hour, and 100 kW above for half an hour.
- Power: 1,200 kW minus 900 kW = 300 kW of discharge power.
- Energy to deliver: 300 kWh + 200 kWh + 50 kWh = 550 kWh.
- Usable fraction of 90%: 550 / 0.9 ≈ 611 kWh of nameplate capacity.
- End-of-life capacity of 80%: 611 / 0.8 ≈ 764 kWh, so a product in the 750 to 800 kWh class would be a starting point.
Duration is then about 764 / 300 = 2.5 hours. The numbers are invented for illustration. A real design uses interval meter data, the manufacturer's usable energy and warranty figures, and a margin for forecast error.
Step 4: Check Codes, Safety and Interconnection
Energy storage installations are covered by standards such as NFPA 855 (installation of stationary energy storage systems), UL 9540 (energy storage systems and equipment) and the NEC (Article 706 for energy storage systems and Article 480 for stationary batteries; in the 2026 NEC the scope of Article 480 covers all stationary batteries, not just standby). Connecting to the grid also needs a utility interconnection review. See NFPA 855 Battery Storage Safety, the Utility Interconnection Process and what changed in the 2026 NEC. Which edition applies depends on your authority having jurisdiction.
Related Sizing Guides
For a home, see Battery Backup Sizing for a House. For data center batteries used beyond UPS backup, see BESS for Data Centers Explained. This article is general education, not a design or a financial analysis.