Both are critical-infrastructure protocols built around timing — but one was built to survive a slow wide-area link between a control center and RTUs scattered across a service territory, and the other was built to trip a breaker in under a millisecond between two relays on the same substation LAN.

DNP3 and IEC 61850 both show up on electric utility networks, both carry safety- and grid-reliability-relevant data, and both are frequently described as "the utility SCADA protocol" — which invites confusion about which one actually does what. They were built for different domains at different distances and timescales. DNP3 (Distributed Network Protocol) originated in electric utility SCADA and telemetry over wide-area links — a control center master polling remote terminal units at substations, pumping stations, and feeders scattered across a service territory, often over serial radio, leased line, or now IP/DNP3 over Ethernet. IEC 61850 originated specifically for substation automation — communication within a single substation, between protection relays (IEDs, Intelligent Electronic Devices) and the station bus, where GOOSE (Generic Object Oriented Substation Event) messaging can trip a circuit breaker in under a millisecond. Same industry, very different design center.