Air-Cooled vs Water-Cooled Chillers
Air-cooled chillers are simple and need no cooling tower. Water-cooled chillers are more efficient at large sizes. Compare efficiency, water use, space and maintenance.
Mechanical, HVAC & Fluids · Last reviewed
Short answer: air-cooled chillers suit small and medium loads, rooftops and sites without water. Water-cooled chillers suit large, long-running loads where their efficiency and long life outweigh the tower, pumps and water treatment they need.
| Air-cooled | Water-cooled | |
|---|---|---|
| Heat rejection | Fans blow outdoor air across condenser coils | Condenser water carries heat to a cooling tower or other sink |
| Efficiency | Lower. Depends on dry-bulb temperature | Higher. Depends on wet-bulb temperature, which is lower than dry-bulb |
| Capacity range | Up to about 500 tons for common units | From about 100 tons to many thousands of tons |
| Added equipment | None, or fans only | Cooling tower, condenser-water pumps, piping, water treatment |
| Water use | None | Makeup water for evaporation, drift and blowdown |
| Space | Outdoors, takes roof or yard area | Chiller inside, tower outside, plus a plant room |
| First cost | Lower for small and medium sizes | Higher for the whole plant, lower per ton at very large sizes |
| Maintenance and life | Fewer systems, shorter equipment life outdoors | More systems to maintain, longer chiller life, Legionella risk management for the tower |
Related tools and labs
Calculators, labs and simulators are part of the All-Access Pass.
Questions
What is a typical efficiency difference?
Water-cooled chillers are commonly rated well below 0.7 kW per ton at design. Air-cooled units are often 1.0 to 1.3 kW per ton or higher. Check the AHRI-rated values for the actual equipment.
Can I use free cooling?
Yes. Both types can use a waterside or airside economizer when outdoor conditions are cool enough, and many plants do.
What is a water-cooled chiller's condenser water temperature based on?
On the outdoor wet-bulb temperature plus the tower approach. A lower wet-bulb temperature gives colder condenser water and higher chiller efficiency.
Can I use a dry cooler or a hybrid system?
Yes. Dry coolers and hybrid (adiabatic) coolers save water, and are chosen where water is scarce or costly.
How does Legionella risk affect the choice?
Cooling towers need a water management plan to control Legionella growth. Air-cooled chillers avoid that task.
Educational material. Examples use simplified, hypothetical inputs and are not a design, a construction document or professional engineering advice. Confirm requirements with the codes and standards adopted where the work is built and with a licensed engineer.