VAV vs CAV: Variable or Constant Air Volume Systems
Constant-volume systems vary the supply temperature. Variable-volume systems vary the airflow. Compare energy use, comfort control, cost and applications.
Mechanical, HVAC & Fluids · Last reviewed
Short answer: CAV is simple and suits spaces with steady loads and tight ventilation needs. VAV saves fan energy where loads vary by zone and time, which is most commercial buildings.
| CAV (constant air volume) | VAV (variable air volume) | |
|---|---|---|
| How it meets load | Fixed airflow. Supply temperature changes (reheat or cycling) | Supply temperature stays fixed. Airflow to each zone changes with the load |
| Fan energy | Fan runs at full flow | Fan slows with demand (VFD). Power falls steeply as airflow falls |
| Zone control | One zone per unit, or reheat for several | Many zones on one air handler through VAV boxes |
| Ventilation | Constant airflow keeps outdoor air steady | Minimum airflow and outdoor-air control are needed so ventilation holds at low load |
| Complexity and cost | Lower first cost, simple controls | Higher first cost: boxes, sensors, static-pressure control |
| Comfort risks | Overcooling or reheat energy at part load | Dumping or poor mixing at low airflow, noise at high airflow |
| Typical use | Labs, operating rooms, small buildings, constant-load process spaces | Offices, schools, hospitals general areas, multi-zone commercial buildings |
Related tools and labs
Calculators, labs and simulators are part of the All-Access Pass.
Questions
Does VAV always use less energy?
Not always. A poorly controlled VAV system with high minimums and fixed static pressure can waste more than a simple CAV system.
Can a lab use VAV?
Yes, with constant-volume or tracked exhaust and controlled minimum flow so room pressure and air change rates hold.
What is a VAV box with reheat?
A terminal unit that varies airflow down to a minimum, and then heats the air when the zone still needs heating. Reheat uses energy, so the minimum airflow should be as low as ventilation rules allow.
What is duct static pressure reset?
A control strategy that lowers the fan's duct static pressure setpoint when the boxes are mostly closed, which saves fan energy.
Do energy codes favor VAV?
Many energy codes limit reheat and fan power in ways that lead large multi-zone systems toward variable air volume. Check the code edition that applies.