Dry-Type vs Liquid-Filled Transformers
Dry-type units suit indoor locations with fewer fire constraints. Liquid-filled units are more compact, efficient at larger sizes and common outdoors. Compare them side by side.
Electrical & Power · Last reviewed
Short answer: dry-type transformers are the usual choice indoors, in buildings and near occupants. Liquid-filled transformers are the usual choice outdoors and for larger ratings, where cooling and cost favor them and fire separation is available.
| Dry-type | Liquid-filled | |
|---|---|---|
| Insulation and cooling | Air with solid insulation (ventilated, cast resin or VPI) | Mineral oil, silicone or natural ester fluid |
| Fire behavior | No liquid fuel load. Fewer fire-separation rules indoors | Fluid can burn. Less-flammable fluids (higher fire point) reduce but do not remove the requirement for separation or containment |
| Size and weight | Larger and heavier for the same rating | More compact |
| Cooling and overload | Lower thermal capacity, sensitive to ambient and ventilation | Good heat removal and overload capacity |
| Losses and cost | Often higher cost per kVA at large ratings | Usually lower cost and losses at medium and large ratings |
| Maintenance | Keep clean and dry | Check fluid level and condition, sample the fluid, and manage leaks |
| Typical use | Indoor and commercial buildings, up to a few MVA | Utility, industrial and outdoor installations, large ratings |
Related tools and labs
Calculators, labs and simulators are part of the All-Access Pass.
More comparisons
- VFD vs Soft Starter: Which One for an AC Induction Motor?
- Star-Delta vs Direct-on-Line Motor Starting
- Copper vs Aluminum Feeders: How to Choose
- MCCB vs ACB: Molded-Case or Air Circuit Breaker?
- VAV vs CAV: Variable or Constant Air Volume Systems
- Air-Cooled vs Water-Cooled Chillers
- Centrifugal vs Positive-Displacement Pumps
- PLC vs DCS: Which Control System for the Plant?
Questions
What is a cast-resin transformer?
A dry-type unit with the windings encapsulated in epoxy resin, which resists moisture and dust and is common indoors in Europe and in many commercial buildings.
Are PCB-filled transformers still in use?
Old units may exist. PCB fluid is regulated and the owner must follow the rules for testing, labeling and disposal.
What is a less-flammable fluid?
A liquid with a higher fire point than mineral oil, such as a natural ester or a silicone fluid. Such fluids lower the fire risk and may reduce the separation or containment requirements, depending on the code.
Can a dry-type transformer be used outdoors?
Yes, in a weatherproof enclosure designed for it. Check the enclosure rating and the ventilation.
How do I compare losses?
Use the guaranteed no-load and load losses and a cost per kW over the evaluation life to find the lifetime cost of each option.