Online vs Line-Interactive UPS: Which One Do You Need?
Online UPS powers the load from its inverter at all times. Line-interactive switches to battery on failure. Compare quality, transfer, efficiency and cost.
Electrical & Power · Last reviewed
Short answer: a line-interactive UPS suits most office workstations, network edge equipment and other loads that can ride through a few milliseconds of transfer. An online UPS suits critical loads that need clean, continuous power, such as server rooms, labs and sensitive process equipment, and it costs more to buy and run.
| Online (double conversion) | Line-interactive | |
|---|---|---|
| How the load is fed | Always from the inverter. Input is rectified, then inverted | From the utility through a voltage regulator. The inverter takes over on a failure |
| Transfer to battery | No transfer time, because the inverter already feeds the load | A few milliseconds, typically within the hold-up time of modern power supplies |
| Power quality at the output | Regenerated, regulated voltage and frequency, isolated from input disturbances | Voltage is corrected by boost and buck. Frequency follows the utility. Small units may give a simulated sine wave on battery |
| Efficiency | Lower in double-conversion mode, with an efficient "eco" mode on many models | Higher, because most of the time only the regulator is in the path |
| Heat and cooling | More heat, so more cooling and ventilation | Less heat |
| Battery stress | The charger runs continuously, and the battery sees the input all the time | Battery is idle on float most of the time |
| Cost and maintenance | Higher purchase cost and more electronics to maintain | Lower purchase cost and simpler |
| Standards class (IEC 62040-3) | VFI: output independent of voltage and frequency | VI: output independent of voltage only |
Related tools and labs
Calculators, labs and simulators are part of the All-Access Pass.
More comparisons
- VFD vs Soft Starter: Which One for an AC Induction Motor?
- Star-Delta vs Direct-on-Line Motor Starting
- Copper vs Aluminum Feeders: How to Choose
- MCCB vs ACB: Molded-Case or Air Circuit Breaker?
- Dry-Type vs Liquid-Filled Transformers
- UPS vs Generator vs Battery Storage: Which Backup Fits?
- VAV vs CAV: Variable or Constant Air Volume Systems
- Air-Cooled vs Water-Cooled Chillers
Questions
Is the transfer time of a line-interactive UPS a problem?
For most computers it is not, because their power supplies ride through a short gap. Check the load specification for sensitive or older equipment.
What is eco mode?
An online UPS can pass utility power directly to the load when it is within limits, and switch to double conversion when it is not. It saves energy with a short transfer in some conditions, so check the manufacturer data.
Educational material. Examples use simplified, hypothetical inputs and are not a design, a construction document or professional engineering advice. Confirm requirements with the codes and standards adopted where the work is built and with a licensed engineer.