START WITH THE FOUNDATIONS

AI Data-Center Foundations

Follow electrical power, compute demand and heat rejection across a data center.

Free · No sign-in required3 lessonsWorked examples & practiceBeginner

0 of 3 lessons checked · Progress is saved in this browser.

  1. 01 / SYSTEM VIEWElectrical supply
  2. 02 / SYSTEM VIEWCompute workload
  3. 03 / SYSTEM VIEWHeat rejection

This map connects the course ideas; it is not a detailed engineering schematic.

LESSON 1 / 3 · FREE

Power paths and boundaries

Your goal: Distinguish connected ratings from measured demand.

Understand the idea

Utility, switchgear, UPS, distribution and rack loads form connected power paths. A rating states an equipment capability under conditions, while demand describes actual loading. Redundant paths do not automatically double usable capacity: survival after a failure depends on the remaining path and its limits.

Worked example

Ten racks averaging 8 kW use 80 kW of IT power. That excludes cooling and other facility loads and does not prove redundancy.

Try it yourself

Twelve racks each average 6 kW. Calculate their combined IT demand.

Does two-path equipment automatically double usable resilient capacity?

Background reference ↗ · Original teaching text and fictional practice values.

Continue to lesson 2: Energy and facility overhead →

LESSON 2 / 3 · FREE

Energy and facility overhead

Your goal: Calculate energy from average power and time.

Understand the idea

Electrical energy accumulates over time. kW is power and kWh is energy. For an explicitly constant average load, energy equals power multiplied by hours. Facility and IT measurements must cover the same interval and compatible boundaries before ratios are compared.

Worked example

An 80 kW average IT load over 10 h uses 800 kWh. A facility total of 1,000 kWh for that same interval gives a facility/IT energy ratio of 1.25.

Try it yourself

A constant average 50 kW load runs for 8 h. Find its energy.

Which comparison is meaningful?

Background reference ↗ · Original teaching text and fictional practice values.

Continue to lesson 3: Heat and operating evidence →

LESSON 3 / 3 · FREE

Heat and operating evidence

Your goal: Relate server electrical input to a simplified heat balance.

Understand the idea

Most server electrical energy ultimately becomes heat inside the defined facility boundary. Cooling performance also depends on airflow, liquid flow, temperatures and equipment behavior. A steady energy balance helps identify missing terms; it does not calculate local chip temperature or prove cooling resilience.

Worked example

A fictional 100 kW IT room adds 5 kW of internal fan heat. Under the simplified stated boundary, heat removal must balance 105 kW at steady conditions.

Try it yourself

For 80 kW IT and 4 kW additional internal heat, calculate the steady heat total.

Does this total predict every GPU temperature?

Background reference ↗ · Original teaching text and fictional practice values.

Choose your next step →

Finish with evidence of your understanding.

Explain each worked example in your own words, check the units and identify one assumption that could change the result. Then use the linked labs or roadmap to apply the ideas to a broader task.

Practice progress is a study aid, not a professional qualification or proof of field competence.

Continue in AI Data Centers

Apply these foundations in an available course, lab or roadmap. The linked resource’s access rules still apply.

Show 3 more available resources

Open the full studio → · Choose another discipline →

About this introductory course

These original lessons use simplified models and explicitly supplied practice values. Calculations teach concepts; they do not select real equipment, establish code compliance or authorize field work. Follow the linked references and advanced resources for deeper study.

Updated · Study progress stays in this browser. There is no certificate or paid gate for these lessons.