Cantilever Beam: Tip Load and Deflection
Find shear, fixed-end moment, bending stress, tip deflection and rotation of a 2 m steel cantilever with a 10 kN end load, checked against L/180.
Civil & Structural · Last reviewed
Given
A steel cantilever of length L = 2.0 m is fixed at one end and carries a concentrated load P = 10 kN at the free end. Ignore self-weight. Section properties (supplied): second moment of area I = 1.94 × 10⁷ mm⁴, section modulus S = 1.94 × 10⁵ mm³, so the extreme fiber is 100 mm from the neutral axis. Modulus of elasticity E = 200 GPa. For this exercise the deflection limit is L ÷ 180.
Find
The reaction shear and moment at the support, the maximum bending stress, the tip deflection and rotation, and whether the deflection limit is met.
Solution
Related tools and labs
Calculators, labs and simulators are part of the All-Access Pass.
More worked problems
- Simply Supported Beam: Reactions, Moment and Deflection
- Column Buckling: Why End Conditions Matter
- Footing Bearing Pressure with an Eccentric Load
- Stormwater Runoff Using the Rational Method
- Earthwork Cut and Fill by the Average-End-Area Method
- Size the Branch Circuit for a 40 hp, 460 V Motor
- Voltage Drop on a 240 V Single-Phase Feeder
- Pump Head, Shaft Power and Motor Size
Questions
Is L/180 a code limit?
No. It is an exercise value. Deflection limits come from the code or the project specification and depend on the use, the member and the finishes it supports.
What is the self-weight effect?
A uniform self-weight w adds a moment of wL² ÷ 2 at the support and a deflection of wL⁴ ÷ 8EI. It is small for a light section but should be included in a real check.
Does this check shear or local buckling?
No. A complete member check includes shear, web and flange buckling, lateral-torsional buckling and the connection.
Educational material. Examples use simplified, hypothetical inputs and are not a design, a construction document or professional engineering advice. Confirm requirements with the codes and standards adopted where the work is built and with a licensed engineer.