GFCI vs AFCI vs Dual-Function Protection
A GFCI protects against shock, an AFCI against arcing fires, and dual-function devices do both. One does not replace the other.
Electrical & Power · Last reviewed
Short answer: a GFCI addresses the risk of electric shock, an AFCI addresses the risk of fire from arcing in wiring and cords, and a dual-function device does both. Install the protection that the code requires for each location. Neither device substitutes for the other.
| GFCI | AFCI | Dual-function (AFCI and GFCI) | |
|---|---|---|---|
| What it detects | Current leaking to ground, shown by an imbalance between the hot and the neutral | The signature of an arcing fault in the wiring or in a cord | Both |
| Hazard addressed | Electric shock and electrocution | Fire from arcing | Shock and fire |
| Typical trip level | About 4 to 6 mA of leakage for personnel protection | Based on arc patterns, not a fixed current | Both behaviors |
| Where required | Wet and damp areas such as bathrooms, kitchens, garages and outdoors, set by the code | Many living areas in homes, set by the code | Where both are required, for example a kitchen |
| Form | Receptacle or circuit breaker | Circuit breaker, or in some cases a receptacle | Circuit breaker, or a combination of devices |
| Not covered | Arcs between the hot and the neutral that do not leak to ground | Shock protection for a person | Overload and short circuit, which the breaker part still handles |
Related tools and labs
Calculators, labs and simulators are part of the All-Access Pass.
More comparisons
- VFD vs Soft Starter: Which One for an AC Induction Motor?
- Star-Delta vs Direct-on-Line Motor Starting
- Copper vs Aluminum Feeders: How to Choose
- MCCB vs ACB: Molded-Case or Air Circuit Breaker?
- Dry-Type vs Liquid-Filled Transformers
- Online vs Line-Interactive UPS: Which One Do You Need?
- VAV vs CAV: Variable or Constant Air Volume Systems
- Air-Cooled vs Water-Cooled Chillers
Questions
Why does my AFCI trip with a vacuum cleaner?
Some motors with brushes produce arcing that looks like a fault. Newer devices distinguish better, but a real wiring fault can also be the cause. Test with other loads.
Do GFCI and AFCI protect equipment?
They are designed for people and for fire. Ground-fault protection of equipment uses higher trip levels, and is a separate device.
Educational material. Examples use simplified, hypothetical inputs and are not a design, a construction document or professional engineering advice. Confirm requirements with the codes and standards adopted where the work is built and with a licensed engineer.