Worked problem

UPS Runtime: Energy, Efficiency and Usable Capacity

Estimate the runtime of a 2 kW load on a 48 V, 100 Ah battery bank from usable capacity and inverter efficiency, and see the limits of the model.

Electrical & Power · Last reviewed

Given

A constant 2.0 kW load runs from a 48 V (nominal), 100 Ah battery bank through an inverter. For this exercise assume 80% of the nominal capacity is usable before the battery must stop discharging, and an inverter efficiency of 92%.

Find

The estimated runtime, and what the answer depends on.

Solution

  1. Nominal stored energy = 48 V × 100 Ah = 4,800 Wh.
  2. Usable energy = 0.80 × 4,800 = 3,840 Wh.
  3. Power taken from the battery = 2,000 ÷ 0.92 = 2,174 W, because the inverter has losses.
  4. Runtime = 3,840 ÷ 2,174 = 1.77 h, about 106 minutes.
  5. Discharge current at nominal voltage = 2,174 ÷ 48 = 45.3 A, which is 0.45C for a 100 Ah bank. Compare it with the discharge rating of the battery.

Answer

about 1.77 h (roughly 106 minutes) | discharge about 45 A
Usable fractionRuntime
50%66 min
70%93 min
80% (this problem)106 min
90%119 min

Where the simple energy model fails

  • Capacity depends on discharge rate. A 100 Ah rating is normally quoted at a slow rate such as 10 or 20 hours. At 0.45C a lead-acid battery delivers noticeably less than 100 Ah.
  • The battery voltage falls as it discharges. For a constant-power load the current rises as the voltage falls, which shortens the runtime further.
  • Low temperature, battery age and the end-of-discharge voltage setting all reduce usable capacity. A battery at the end of its life has about 80% of its original capacity.
  • Inverter efficiency changes with load. Fans, charger and controls draw power too.

Use the energy estimate to compare options, and the manufacturer discharge table (watts per cell to a stated end voltage) for a runtime you will rely on.

Related tools and labs

Calculators, labs and simulators are part of the All-Access Pass.

More worked problems

Questions

Why not use the full 4,800 Wh?

Discharging a battery to empty shortens its life and may not be possible, because the inverter or battery management stops at a minimum voltage. The usable fraction is a planning assumption.

How do I get a longer runtime?

Add battery capacity, reduce the load, or use batteries rated for a higher discharge rate. Doubling the energy roughly doubles the runtime in this model.

Is the usable fraction a code requirement?

No. Here it is an exercise input. Battery makers give the real limits for their product.