Challenge: The Current That Looks Too High
An engineer calculates a three-phase line current as 37.5 A for a 12 kW load. Find the error before opening the answer.
Electrical & Power · Last reviewed
An engineer estimates the line current of a balanced three-phase load with:
- Three-phase electrical real input power: 12 kW.
- Line-to-line voltage: 400 V.
- Power factor: 0.80.
Your task: find the error, calculate the correct line current, and say whether motor efficiency belongs in this calculation.
Related tools and labs
Calculators, labs and simulators are part of the All-Access Pass.
More worked problems
- Size the Branch Circuit for a 40 hp, 460 V Motor
- Voltage Drop on a 240 V Single-Phase Feeder
- Office Lighting Load: Connected Power and Current
- Size a Three-Phase Transformer for a Mixed Load
- Power Factor Correction: How Many kvar of Capacitors?
- Short-Circuit Current at a Transformer Secondary
- Pump Head, Shaft Power and Motor Size
- Sensible Cooling Capacity from Airflow and Temperature Difference
Questions
When is √3 not used?
For single-phase, and when working from the phase voltage of a balanced three-phase load, where P = 3 × V(phase) × I(phase) × PF.
How do I convert kVA to amps for a three-phase load?
Divide kVA × 1000 by (√3 × line-to-line voltage). For 100 kVA at 480 V, that is 100,000 ÷ (1.732 × 480) = 120 A.
What is the difference between kW and kVA?
kW is real power that does work. kVA is apparent power, the product of voltage and current. kW = kVA × power factor.
Does it matter whether the load is wye or delta connected?
Not for the line current when you use line-to-line voltage and the total power. The wye or delta connection changes the current in each winding, not the line current formula.