Power Factor Correction: How Many kvar of Capacitors?
Find the capacitor kvar needed to raise a 500 kW load from 0.80 to 0.95 power factor, and the drop in apparent power and line current.
Electrical & Power · Last reviewed
Given
A 480 V, 3-phase facility draws 500 kW at a power factor of 0.80 lagging. The utility asks for 0.95 or better.
Find
The capacitor kvar to add, and the change in apparent power and line current.
Solution
Related tools and labs
Calculators, labs and simulators are part of the All-Access Pass.
More worked problems
- Size the Branch Circuit for a 40 hp, 460 V Motor
- Voltage Drop on a 240 V Single-Phase Feeder
- Office Lighting Load: Connected Power and Current
- Challenge: The Current That Looks Too High
- Size a Three-Phase Transformer for a Mixed Load
- Short-Circuit Current at a Transformer Secondary
- Pump Head, Shaft Power and Motor Size
- Sensible Cooling Capacity from Airflow and Temperature Difference
Questions
Does power factor correction reduce real power use?
It reduces the current and the losses in the supply conductors and transformer, which is a small saving. It mainly cuts the apparent power, which is what many utilities bill against.
Does it lower the current inside the plant?
Only upstream of the capacitors. Loads on the load side of the bank still draw their original current.
Where should the capacitors be installed?
At the individual load, at a motor control center, or at the service. Capacitors at the load cut current in the most conductors but cost more per kvar. A central bank at the service is simpler and can switch in stages.
What is a detuned or filtered capacitor bank?
A bank with series reactors that moves its resonant frequency away from the harmonics present, which prevents resonance in systems with drives and other nonlinear loads.
What does a power factor penalty look like?
Utility rules differ. Many bill on peak kVA or add a charge when the power factor falls below a threshold such as 0.90 or 0.95. Check the tariff.