Office Lighting Load: Connected Power and Current
A short project: total the connected lighting power for three spaces, convert to apparent power and estimate the current, then write the calculation up so another engineer can check it.
Electrical & Power · Last reviewed
Brief
A hypothetical office has three spaces. Calculate the connected lighting input power and estimate the current on a simplified single-phase supply. This exercise covers the arithmetic only. It leaves out code-based demand factors, circuit and phase allocation, conductor sizing, protection, emergency lighting and installation design.
Given
| Space | Luminaires | Input power each |
|---|---|---|
| Open office | 24 | 32 W |
| Meeting room | 8 | 25 W |
| Corridor | 10 | 18 W |
Assume all luminaires operate at once, the supply is 120 V single-phase and the power factor is 0.95. Treat these as fixed exercise inputs.
Worksheet
| Item | Your result |
|---|---|
| Open-office connected power | ____ W |
| Meeting-room connected power | ____ W |
| Corridor connected power | ____ W |
| Total connected real power | ____ W |
| Apparent power (real power ÷ power factor) | ____ VA |
| Estimated current (apparent power ÷ voltage) | ____ A |
Related tools and labs
Calculators, labs and simulators are part of the All-Access Pass.
More worked problems
- Size the Branch Circuit for a 40 hp, 460 V Motor
- Voltage Drop on a 240 V Single-Phase Feeder
- Challenge: The Current That Looks Too High
- Size a Three-Phase Transformer for a Mixed Load
- Power Factor Correction: How Many kvar of Capacitors?
- Short-Circuit Current at a Transformer Secondary
- Pump Head, Shaft Power and Motor Size
- Sensible Cooling Capacity from Airflow and Temperature Difference
Questions
Why 120 V?
It keeps the arithmetic simple. Many commercial lighting circuits run at 277 V instead, and the same method applies with the voltage changed.
Is 0.95 a realistic power factor?
It is a fixed exercise input. Real fixtures vary, so use the manufacturer data for a real design.
What is the difference between connected load and demand load?
Connected load is the sum of everything that could run. Demand load is the load the code or the designer expects to run at the same time. Demand is usually the smaller figure.
Why convert watts to volt-amperes?
Wires, breakers and transformers carry current, and current depends on apparent power (volt-amperes), not only real power. Dividing watts by power factor gives the apparent power.
Do LED drivers change the power factor?
Yes. Driver power factor varies by product, from below 0.9 to above 0.95. Use the manufacturer data for a real design.