Solar PV String Voltage on a Cold Day
Correct a module open-circuit voltage for a −10 °C cell temperature and check how many modules in series stay under a 1,000 V inverter limit.
Electrical & Power · Last reviewed
Given
A module has an open-circuit voltage Voc of 49.5 V at standard test conditions (25 °C cell temperature). Its Voc temperature coefficient is −0.27 %/°C. For this exercise take the lowest expected cell temperature as −10 °C. The inverter accepts a maximum DC input voltage of 1,000 V. A designer proposes 20 modules in series.
Find
Whether the proposed string is acceptable, and the largest number of modules that is.
Solution
Related tools and labs
Calculators, labs and simulators are part of the All-Access Pass.
More worked problems
- Size the Branch Circuit for a 40 hp, 460 V Motor
- Voltage Drop on a 240 V Single-Phase Feeder
- Office Lighting Load: Connected Power and Current
- Challenge: The Current That Looks Too High
- Size a Three-Phase Transformer for a Mixed Load
- Power Factor Correction: How Many kvar of Capacitors?
- Pump Head, Shaft Power and Motor Size
- Sensible Cooling Capacity from Airflow and Temperature Difference
Questions
Which temperature should I use?
The lowest cell temperature expected at the site. The code allows specific methods for this, so confirm the method and the edition that apply. The −10 °C here is an exercise value.
Does a larger voltage limit change the answer?
Yes. With a 1,500 V inverter, 27 modules would give 1,463 V cold, so the number of modules depends strongly on the equipment rating.
Does the coefficient apply to current too?
Current has its own small positive coefficient. It matters for the maximum-current checks, not for this voltage check.