Unbalanced Three-Phase Loads: Find the Neutral Current
Calculate the neutral current for phase currents of 100 A, 80 A and 60 A at unity power factor, and see why adding the magnitudes gives the wrong answer.
Electrical & Power · Last reviewed
Given
A three-phase, four-wire wye system with balanced sinusoidal line voltages. The phase currents are Ia = 100 A, Ib = 80 A and Ic = 60 A, all at unity power factor, so each current is in phase with its own phase voltage. There are no harmonics.
Find
The current in the neutral conductor.
Solution
Related tools and labs
Calculators, labs and simulators are part of the All-Access Pass.
More worked problems
- Size the Branch Circuit for a 40 hp, 460 V Motor
- Voltage Drop on a 240 V Single-Phase Feeder
- Office Lighting Load: Connected Power and Current
- Challenge: The Current That Looks Too High
- Size a Three-Phase Transformer for a Mixed Load
- Power Factor Correction: How Many kvar of Capacitors?
- Pump Head, Shaft Power and Motor Size
- Sensible Cooling Capacity from Airflow and Temperature Difference
Questions
Can the neutral current be larger than a phase current?
Yes. With triplen harmonics, or a severe imbalance such as one phase loaded and the other two empty, the neutral can match or exceed a phase current.
Does this apply to a delta system?
A delta system has no neutral. The same phasor idea applies to the currents at a wye point or at a transformer with a neutral.
Does this size the neutral conductor?
No. Neutral sizing follows the code rules, including how harmonic loads are treated.
Educational material. Examples use simplified, hypothetical inputs and are not a design, a construction document or professional engineering advice. Confirm requirements with the codes and standards adopted where the work is built and with a licensed engineer.