Fault Current at the End of a Feeder
Add a 150 ft copper feeder to the transformer fault calculation and compare the fault current at the terminals with the current at a downstream panel.
Electrical & Power · Last reviewed
Given
The 500 kVA, 480 V, 5.75% impedance transformer from the short-circuit problem in this section, on an infinite bus. One 500 kcmil copper conductor per phase in steel conduit runs 150 ft to a downstream panel. For this exercise take the feeder impedance as R = 0.027 Ω and X = 0.048 Ω per 1,000 ft per phase; real values come from the code tables or the cable maker. Treat the transformer impedance as reactance.
Find
The three-phase fault current at the transformer terminals and at the downstream panel.
Solution
Related tools and labs
Calculators, labs and simulators are part of the All-Access Pass.
More worked problems
- Size the Branch Circuit for a 40 hp, 460 V Motor
- Voltage Drop on a 240 V Single-Phase Feeder
- Office Lighting Load: Connected Power and Current
- Challenge: The Current That Looks Too High
- Size a Three-Phase Transformer for a Mixed Load
- Power Factor Correction: How Many kvar of Capacitors?
- Pump Head, Shaft Power and Motor Size
- Sensible Cooling Capacity from Airflow and Temperature Difference
Questions
Why does the fault current fall with distance?
The feeder conductors add impedance in series with the transformer, so the same voltage drives a smaller current.
Should I use the lower value to choose equipment?
Equipment should be rated for the highest fault current it can see. The value at the transformer terminals is the safe upper bound for everything downstream.
What changes with a finite utility source?
The source impedance adds to the total, which lowers the fault current at every point.