Electrical Distribution & Protection Workbench

A connected electrical distribution study that follows three load groups through a transformer and feeder. It combines coincidence, power factor, voltage drop, conductor losses and a simple transformer-terminal fault estimate so the relationships remain visible. The results identify capacity and voltage-drop sensitivities at stated boundaries. A current below a breaker nameplate does not prove conductor protection or selectivity, and the transformer-terminal fault estimate is not a remote fault-duty or arc-flash calculation.

Published and reviewed · EngineersUniverse · Interactive workspace · All-Access ↓ · Worked example ↓

About this workbench

What it is and its purpose
A connected electrical distribution study that follows three load groups through a transformer and feeder. It combines coincidence, power factor, voltage drop, conductor losses and a simple transformer-terminal fault estimate so the relationships remain visible.
Who it is for
For electrical designers, facilities engineers, technical students and project reviewers who need to explain why load, voltage, impedance and feeder route matter together. It is an early study and teaching environment rather than a finished protection design.
When and where to use it
Use it while comparing a commercial feeder route, reviewing an initial load budget or preparing questions for a detailed power-system study. It helps reveal a long-feeder voltage problem even when transformer kVA appears adequate.
How to use it
Start with the commercial feeder. Enter connected lighting, HVAC and process loads, apply your justified coincidence factor, then review power factor and transformer data. Change feeder length or resistance and capture a baseline to compare voltage drop, current and losses.
What the results mean
The results identify capacity and voltage-drop sensitivities at stated boundaries. A current below a breaker nameplate does not prove conductor protection or selectivity, and the transformer-terminal fault estimate is not a remote fault-duty or arc-flash calculation.
Continue to the interactive workspace ↓

Build a transparent load budget

Demand kW equals the sum of connected groups times the entered coincidence percentage. Demand kVA is kW divided by lagging power factor. The same coincidence factor applies to all groups in this study; it is not a substitute for the demand rules of a particular adopted code.

Trace the balanced feeder

For a balanced lagging three-phase load, current is kVA × 1000 / (√3 × line-to-line voltage). Approximate voltage drop is √3 × I × L × (R cosφ + X sinφ), with route length in km and per-conductor R/X in Ω/km. Real conductor loss is 3I²R L. Neutral imbalance and harmonics are excluded.

Separate load and fault boundaries

Transformer loading compares demand kVA with nameplate kVA. Terminal short-circuit current is transformer full-load current divided by per-unit impedance, assuming an infinite upstream source. Actual source impedance and the downstream feeder reduce or otherwise change real fault conditions; motor contribution and X/R effects are not included.

Protection requires more than a rating

The breaker and voltage-drop thresholds are editable study screens. Real design still needs conductor ampacity and correction factors, interrupting ratings, trip curves, fault clearing, grounding, selectivity and applicable installation rules. Keep equipment documentation with the final engineering study.

Worked example

  1. 45 + 120 + 90 = 255 kW connected. At 80% coincidence, demand is 204 kW; at PF 0.9, apparent demand is 226.667 kVA.
  2. At 480 V three-phase, current is approximately 272.638 A. With 100 m route, R = 0.125 Ω/km and X = 0.08 Ω/km, the model predicts about 6.959 V drop, or 1.450%.
  3. A 500 kVA transformer is 45.333% loaded. Its full-load current is about 601.407 A; at 5.75% impedance the infinite-source terminal estimate is 10.459 kA. This is a separate boundary from the feeder end.

Questions and interpretation

Does this coordinate protective devices?

No. It compares load current with an entered rating but has no time-current curves, clearing times or selective-coordination logic.

Can I enter one-way cable length?

Yes. The three-phase formula uses one-way route length and per-conductor impedance. Do not double the length as for a two-wire DC loop.

Where do R and X come from?

Use the actual cable arrangement, conductor material, temperature and manufacturer impedance data. Default values are illustrative.

Prepare an activity report

Use View / print study report to review a clean summary of your activity, then print it or save a PDF. Download study report (PDF) creates a formatted document with the actual assumptions, results, interpretation and references. Charts and baseline comparisons are included where applicable; security reports summarize recorded runs. Website navigation, purchase panels and unrelated page content are excluded.

References and verification

The linked sources explain the background. The interactive calculations and scenarios are original teaching exercises with explicit assumptions, not certified equipment selection, measured performance or a real security assessment.