Build a transparent load budget
Demand kW equals the sum of connected groups times the entered coincidence percentage. Demand kVA is kW divided by lagging power factor. The same coincidence factor applies to all groups in this study; it is not a substitute for the demand rules of a particular adopted code.
Trace the balanced feeder
For a balanced lagging three-phase load, current is kVA × 1000 / (√3 × line-to-line voltage). Approximate voltage drop is √3 × I × L × (R cosφ + X sinφ), with route length in km and per-conductor R/X in Ω/km. Real conductor loss is 3I²R L. Neutral imbalance and harmonics are excluded.
Separate load and fault boundaries
Transformer loading compares demand kVA with nameplate kVA. Terminal short-circuit current is transformer full-load current divided by per-unit impedance, assuming an infinite upstream source. Actual source impedance and the downstream feeder reduce or otherwise change real fault conditions; motor contribution and X/R effects are not included.
Protection requires more than a rating
The breaker and voltage-drop thresholds are editable study screens. Real design still needs conductor ampacity and correction factors, interrupting ratings, trip curves, fault clearing, grounding, selectivity and applicable installation rules. Keep equipment documentation with the final engineering study.
Worked example
- 45 + 120 + 90 = 255 kW connected. At 80% coincidence, demand is 204 kW; at PF 0.9, apparent demand is 226.667 kVA.
- At 480 V three-phase, current is approximately 272.638 A. With 100 m route, R = 0.125 Ω/km and X = 0.08 Ω/km, the model predicts about 6.959 V drop, or 1.450%.
- A 500 kVA transformer is 45.333% loaded. Its full-load current is about 601.407 A; at 5.75% impedance the infinite-source terminal estimate is 10.459 kA. This is a separate boundary from the feeder end.
Questions and interpretation
Does this coordinate protective devices?
No. It compares load current with an entered rating but has no time-current curves, clearing times or selective-coordination logic.
Can I enter one-way cable length?
Yes. The three-phase formula uses one-way route length and per-conductor impedance. Do not double the length as for a two-wire DC loop.
Where do R and X come from?
Use the actual cable arrangement, conductor material, temperature and manufacturer impedance data. Default values are illustrative.
Prepare an activity report
Use View / print study report to review a clean summary of your activity, then print it or save a PDF. Download study report (PDF) creates a formatted document with the actual assumptions, results, interpretation and references. Charts and baseline comparisons are included where applicable; security reports summarize recorded runs. Website navigation, purchase panels and unrelated page content are excluded.
References and verification
The linked sources explain the background. The interactive calculations and scenarios are original teaching exercises with explicit assumptions, not certified equipment selection, measured performance or a real security assessment.
Continue the study
Explore the other workbenches
- HVAC System & Energy Workbench
- Pump & Piping System Workbench
- Fire Alarm System Design Workbench
- Motor & Drive Selection Workbench
- Structural Beam & Load Path Workbench
- Solar & Battery Microgrid Workbench
- SCADA & Control Loop Workbench
- GPU Memory / VRAM Sizing Calculator
- 800 VDC Power Architecture Explorer
- AI Agent Identity & Security Lab
- Data-Center Water & Energy Comparison
- Inside a Liquid-Cooling System / CDU