HVAC System & Energy Workbench

A cooling-system study connecting envelope conductance, internal gains and outdoor-air conditions to coil load, supply airflow and electricity. It separates sensible heat from latent heat and adds fan input outside the cooling-only COP boundary. The study exposes load and energy sensitivities. Annual electricity uses an explicit equivalent input load factor; it is not a weather forecast, seasonal efficiency rating or guarantee of actual energy savings.

Published and reviewed · EngineersUniverse · Interactive workspace · All-Access ↓ · Worked example ↓

About this workbench

What it is and its purpose
A cooling-system study connecting envelope conductance, internal gains and outdoor-air conditions to coil load, supply airflow and electricity. It separates sensible heat from latent heat and adds fan input outside the cooling-only COP boundary.
Who it is for
For HVAC students, mechanical designers, building operators and energy reviewers who want to see how thermal loads and equipment assumptions interact. It supports concept comparison and learning, not final equipment selection or ventilation compliance.
When and where to use it
Use it for a warm design-hour comparison, an early equipment-efficiency discussion or an explanation of why humid outdoor air affects coil duty. It is useful before a full hourly building simulation or psychrometric coil selection.
How to use it
Choose the office example, review temperatures and humidity difference, then expand thermal loads and equipment. Capture a baseline before changing COP, fan pressure or airflow assumptions. Review capacity margin and the separate sensible/latent contributions.
What the results mean
The study exposes load and energy sensitivities. Annual electricity uses an explicit equivalent input load factor; it is not a weather forecast, seasonal efficiency rating or guarantee of actual energy savings.
Continue to the interactive workspace ↓

Define the room and outdoor-air boundary

Envelope sensible heat is UA × outdoor-minus-indoor temperature. Internal sensible gains are entered directly. Ventilation sensible heat uses air density 1.2 kg/m³ and specific heat 1.006 kJ/(kg·K). Solar gains, infiltration and thermal storage are not automatically added.

Keep latent load separate

Outdoor-air latent heat uses density × airflow × 2500 kJ/kg × humidity-ratio difference. The humidity input is g/kg dry air and is converted to kg/kg. Add internal latent gains separately. This simplified balance does not locate a coil state on a psychrometric chart or calculate condensate conditions.

Connect supply air and cooling capacity

Supply airflow is sensible load divided by density, specific heat and room-to-supply temperature difference. The total coil load is sensible plus latent. Compare it with the entered thermal capacity. Outdoor air exceeding total calculated supply triggers an inconsistent-airflow message.

Make annual assumptions visible

Cooling electric input is coil thermal load divided by cooling-only COP. Fan input is flow × total pressure rise / total fan efficiency. The annual estimate multiplies their sum by operating hours and an equivalent input load factor. Part-load curves, economizer hours and weather bins require a more detailed model.

Worked example

  1. With UA 900 W/K and 35 °C outdoors versus 24 °C indoors, envelope load is 9.9 kW. Internal sensible gains are 18 kW.
  2. At 0.5 m³/s outdoor air, ventilation sensible load is 6.640 kW. Internal latent 2 kW plus a 5 g/kg humidity difference adds 9.5 kW latent; total coil duty is about 44.040 kW.
  3. A 10 K room-to-supply difference requires about 2.861 m³/s supply air. At COP 3.5 and 650 Pa / 60% fan efficiency, combined design input is about 15.68 kW. The entered annual factor, not a weather simulation, scales this value.

Questions and interpretation

Is this a full cooling-load calculation?

No. It is a transparent steady-state balance. Use a complete load method for solar, occupancy schedules, constructions, infiltration, diversity and thermal mass.

Does the COP include the fan?

In this model it excludes the separately entered supply fan. Check the boundary of any equipment rating before using it.

Why does humidity increase cooling demand?

Removing moisture requires latent heat removal. The study adds outdoor-air moisture difference and internal latent gains independently.

Prepare an activity report

Use View / print study report to review a clean summary of your activity, then print it or save a PDF. Download study report (PDF) creates a formatted document with the actual assumptions, results, interpretation and references. Charts and baseline comparisons are included where applicable; security reports summarize recorded runs. Website navigation, purchase panels and unrelated page content are excluded.

References and verification

The linked sources explain the background. The interactive calculations and scenarios are original teaching exercises with explicit assumptions, not certified equipment selection, measured performance or a real security assessment.