Define the room and outdoor-air boundary
Envelope sensible heat is UA × outdoor-minus-indoor temperature. Internal sensible gains are entered directly. Ventilation sensible heat uses air density 1.2 kg/m³ and specific heat 1.006 kJ/(kg·K). Solar gains, infiltration and thermal storage are not automatically added.
Keep latent load separate
Outdoor-air latent heat uses density × airflow × 2500 kJ/kg × humidity-ratio difference. The humidity input is g/kg dry air and is converted to kg/kg. Add internal latent gains separately. This simplified balance does not locate a coil state on a psychrometric chart or calculate condensate conditions.
Connect supply air and cooling capacity
Supply airflow is sensible load divided by density, specific heat and room-to-supply temperature difference. The total coil load is sensible plus latent. Compare it with the entered thermal capacity. Outdoor air exceeding total calculated supply triggers an inconsistent-airflow message.
Make annual assumptions visible
Cooling electric input is coil thermal load divided by cooling-only COP. Fan input is flow × total pressure rise / total fan efficiency. The annual estimate multiplies their sum by operating hours and an equivalent input load factor. Part-load curves, economizer hours and weather bins require a more detailed model.
Worked example
- With UA 900 W/K and 35 °C outdoors versus 24 °C indoors, envelope load is 9.9 kW. Internal sensible gains are 18 kW.
- At 0.5 m³/s outdoor air, ventilation sensible load is 6.640 kW. Internal latent 2 kW plus a 5 g/kg humidity difference adds 9.5 kW latent; total coil duty is about 44.040 kW.
- A 10 K room-to-supply difference requires about 2.861 m³/s supply air. At COP 3.5 and 650 Pa / 60% fan efficiency, combined design input is about 15.68 kW. The entered annual factor, not a weather simulation, scales this value.
Questions and interpretation
Is this a full cooling-load calculation?
No. It is a transparent steady-state balance. Use a complete load method for solar, occupancy schedules, constructions, infiltration, diversity and thermal mass.
Does the COP include the fan?
In this model it excludes the separately entered supply fan. Check the boundary of any equipment rating before using it.
Why does humidity increase cooling demand?
Removing moisture requires latent heat removal. The study adds outdoor-air moisture difference and internal latent gains independently.
Prepare an activity report
Use View / print study report to review a clean summary of your activity, then print it or save a PDF. Download study report (PDF) creates a formatted document with the actual assumptions, results, interpretation and references. Charts and baseline comparisons are included where applicable; security reports summarize recorded runs. Website navigation, purchase panels and unrelated page content are excluded.
References and verification
The linked sources explain the background. The interactive calculations and scenarios are original teaching exercises with explicit assumptions, not certified equipment selection, measured performance or a real security assessment.
Continue the study
Explore the other workbenches
- Electrical Distribution & Protection Workbench
- Pump & Piping System Workbench
- Fire Alarm System Design Workbench
- Motor & Drive Selection Workbench
- Structural Beam & Load Path Workbench
- Solar & Battery Microgrid Workbench
- SCADA & Control Loop Workbench
- GPU Memory / VRAM Sizing Calculator
- 800 VDC Power Architecture Explorer
- AI Agent Identity & Security Lab
- Data-Center Water & Energy Comparison
- Inside a Liquid-Cooling System / CDU