Understand the process model
The normalized process starts at 50%. Its equilibrium is 50 + process gain × (delayed output − 50) plus an additive disturbance after 60 seconds. A first-order response with the entered time constant is integrated at 0.25 s intervals; dead time is rounded to the nearest step. Only positive process gains are supported.
Read controller terms
Error is setpoint minus measurement. The controller uses Kp times error plus integral divided by integral time minus derivative time times filtered measurement rate, with a 50% bias. Derivative on measurement avoids a setpoint derivative kick; a one-second derivative filter reduces abrupt measurement changes.
Inspect limits and failure behavior
Output is clamped to 0–100%. Conditional integration prevents further windup when saturation and error push in the same direction. A dropout between 80 and 110 seconds freezes measurement, actuator command and integral; a bias fault instead adds 15 percentage points to measurement. Recovery can therefore produce a transient.
Interpret alarms and performance
The deviation alarm uses absolute setpoint-minus-measured value against the entered band. Integrated absolute error uses the true process value, exposing a distinction during faults. Saturation time and final error supplement the trend, but no safety integrity, network behavior, real PLC scan or industrial alarm rationalization is modeled.
Worked example
- With gain 1, time constant 20 s and delay 2 s, an actuator change of 10 percentage points changes eventual process equilibrium by 10 points before disturbance.
- The reference PI uses Kp = 2, integral time 20 s and no derivative. Setpoint rises from 50% to 65% at 10 s, then a −10-point process disturbance arrives at 60 s.
- During the dropout preset, measurement and command are held from 80–110 s. Compare the true PV line with the held measured line and inspect the recovery; the detailed sample records the fault state.
Questions and interpretation
Does this connect to a PLC?
No. All calculations are a local offline simulation. No commands or telemetry are sent to equipment.
Why show true and measured values?
A real controller only sees its sensor. Showing the hidden model value makes measurement faults and misleading alarms understandable in a teaching study.
Can I transfer these tuning values to a plant?
No. Gain, units, dynamics, actuator behavior and safeguards differ. Real tuning requires an authorized procedure and appropriate engineering review.
Prepare an activity report
Use View / print study report to review a clean summary of your activity, then print it or save a PDF. Download study report (PDF) creates a formatted document with the actual assumptions, results, interpretation and references. Charts and baseline comparisons are included where applicable; security reports summarize recorded runs. Website navigation, purchase panels and unrelated page content are excluded.
References and verification
The linked sources explain the background. The interactive calculations and scenarios are original teaching exercises with explicit assumptions, not certified equipment selection, measured performance or a real security assessment.
Continue the study
Explore the other workbenches
- Electrical Distribution & Protection Workbench
- HVAC System & Energy Workbench
- Pump & Piping System Workbench
- Fire Alarm System Design Workbench
- Motor & Drive Selection Workbench
- Structural Beam & Load Path Workbench
- Solar & Battery Microgrid Workbench
- GPU Memory / VRAM Sizing Calculator
- 800 VDC Power Architecture Explorer
- AI Agent Identity & Security Lab
- Data-Center Water & Energy Comparison
- Inside a Liquid-Cooling System / CDU