Separate standby and alarm states
Sum panel current and device counts times current per device for each state. Notification devices are modeled off in standby and active together in alarm. Detector and module alarm currents use the entered values for every device; real system alarm diversity and auxiliary loads must follow the actual equipment documentation.
Calculate ampere-hours without hiding time
Battery requirement is (standby amps × standby hours + alarm amps × alarm minutes/60) × the entered allowance. Compare with selected Ah. Two equal 12 V batteries in series provide 24 V at the same Ah rating, not twice the Ah. Duration, allowance, temperature and battery aging must be justified for the installation.
Check the notification boundary
Notification current equals appliance quantity times entered alarm mA divided by 1000. End voltage is minimum alarm supply minus total current times outgoing-plus-return resistance. All loads are conservatively lumped at the far end; distributed circuits need a segment-by-segment calculation. Pulsed currents and synchronization are not modeled.
Read an event as a sequence
Normal means monitoring with appliances off. A smoke or manual event commands the example notification circuit on. An open notification circuit reports trouble rather than a fire alarm. This simplified single-zone sequence does not program a real panel, release suppression or validate a full building cause-and-effect matrix.
Worked example
- 40 detectors at 0.1 mA, 8 modules at 0.5 mA and 0.15 A panel current give 0.158 A standby.
- Alarm current is 0.3 A panel + 0.200 A detectors + 0.080 A modules + 0.960 A appliances = 1.540 A. For 24 h standby, 5 min alarm and 1.25 allowance, required capacity is about 4.900 Ah.
- At 20.4 V minimum supply and 2 Ω total loop resistance, 0.96 A notification current gives 18.48 V at the lumped end load. Compare this with the entered 16 V minimum; the result does not establish device compatibility.
Questions and interpretation
Are 24 hours and 5 minutes always required?
No. They are illustrative default durations. Use the adopted requirements and actual system/application, and document the basis with the reviewing authority.
Does an open circuit count as a fire alarm?
The example treats it as a supervised trouble. Actual panel behavior and fault tolerance depend on the listed circuit class and programming.
Can I select the battery solely from Ah?
No. Check charger limits, enclosure space, approved battery type, temperature, aging, voltage and manufacturer documentation.
Prepare an activity report
Use View / print study report to review a clean summary of your activity, then print it or save a PDF. Download study report (PDF) creates a formatted document with the actual assumptions, results, interpretation and references. Charts and baseline comparisons are included where applicable; security reports summarize recorded runs. Website navigation, purchase panels and unrelated page content are excluded.
References and verification
The linked sources explain the background. The interactive calculations and scenarios are original teaching exercises with explicit assumptions, not certified equipment selection, measured performance or a real security assessment.
Continue the study
Explore the other workbenches
- Electrical Distribution & Protection Workbench
- HVAC System & Energy Workbench
- Pump & Piping System Workbench
- Motor & Drive Selection Workbench
- Structural Beam & Load Path Workbench
- Solar & Battery Microgrid Workbench
- SCADA & Control Loop Workbench
- GPU Memory / VRAM Sizing Calculator
- 800 VDC Power Architecture Explorer
- AI Agent Identity & Security Lab
- Data-Center Water & Energy Comparison
- Inside a Liquid-Cooling System / CDU