Separate transport delivery from application effects
This lab models an application consumer, not an MQTT broker, OPC UA stack or HTTP client. An event ID plus payload identifies an accepted update. With deduplication enabled, identical repeats are ignored and changed payloads reusing an accepted ID are rejected.
Map units and time explicitly
Temperature accepts C/F and outputs degrees Celsius. Pressure accepts bar/kPa and outputs kPa. Unknown tags, unsupported units, missing numeric values and malformed timezone-qualified timestamps are not guessed. The older-event policy compares against the last applied timestamp for the mapped tag.
Make retries bounded
A retry allowance of 1 permits 2 total attempts. Simulated failures before success exceeding that allowance leave the event unapplied. Only accepted updates enter the deduplication ledger. Run results are replaced explicitly when you change assumptions and run again.
Inspect rejected events individually
A summary count does not tell you whether a message failed mapping, validation, ordering or acknowledgement. Read the per-event decision table and correct the relevant source or policy; do not assume that increasing retries resolves a unit error.
Worked example
- Run the seven example messages with temperature mapping, deduplication and older-event rejection enabled, zero failures and one retry allowed.
- E1 applies 20 °C. E2 converts 77 °F to 25 °C. Its repeated payload is ignored. The older E3 is rejected; E4 has an unsupported unit; E5 is unmapped; E6 is invalid.
- Two updates apply. Set simulated failures before success to 2 with 1 retry: valid events exhaust 2 attempts without applying. No API calls, credentials or network messages are sent.
Questions and interpretation
Can I use my own data?
The three dashboards and integration lab accept bounded CSV/JSON data matching their downloadable templates. The production and portal demos use explicit local scenario controls; all six can export their activity or dataset. No analysis-service upload is used.
Does this connect to my company systems?
No. These are original local tools and teaching simulations. Existing website access and analytics still apply. Real PLC, ERP, MES or customer-account connections would be a separate implementation.
What is saved?
Working state is session-local. Download CSV/JSON or a formatted report before leaving. No automatic cross-device or cloud synchronization is included.
Prepare an activity report
Use View / print study report to review a clean summary of your activity, then print it or save a PDF. Download study report (PDF) creates a formatted document with the actual assumptions, results, interpretation and references. Charts and baseline comparisons are included where applicable; security reports summarize recorded runs. Website navigation, purchase panels and unrelated page content are excluded.
References and verification
The linked sources explain the background. The interactive calculations and scenarios are original teaching exercises with explicit assumptions, not certified equipment selection, measured performance or a real security assessment.
Continue the study
Explore the other workbenches
- Industrial Operations Dashboard
- Asset & Maintenance Dashboard
- Building Energy & Utilities Dashboard
- ERP-to-MES Production Workflow Lab
- Client Service Portal Workflow Demo
- Graph Digitizer & Test Report Workbench
- Electrical Distribution & Protection Workbench
- HVAC System & Energy Workbench
- Pump & Piping System Workbench
- Fire Alarm System Design Workbench
- Motor & Drive Selection Workbench
- Structural Beam & Load Path Workbench
- Solar & Battery Microgrid Workbench
- SCADA & Control Loop Workbench
- GPU Memory / VRAM Sizing Calculator
- 800 VDC Power Architecture Explorer
- AI Agent Identity & Security Lab
- Data-Center Water & Energy Comparison
- Inside a Liquid-Cooling System / CDU